background image

 

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour (Cubic Meters per Hour) for Gas Pressures of 0.5 psig (3.5 kPa) or Less, 

 

and a Pressure Drop of 0.5 Inch Water Column (124.4 Pa)

 

 

(Based on a 0.60 Specifi c Gravity Gas)

 Nominal  

 

 

Iron 

Internal 

Length of Pipe,  Feet (meters)  

 

  

Pipe Size

 

Dia.

 10 20 30 40 50 60 70 80 90 100 

125 

150 

175 

200

  in. 

in. 

(3.0)  (6.1)  (9.1)  (12.2) (15.2) (18.3) (21.3) (24.4) (27.4) (30.5) (38.1) (45.7) (53.3) (61.0)

 

 

1/2 

0.622 

175 

120 97 82 73 66 61 57 53 50 44 40 37 35

   

 

(4.96) (3.40) (2.75) (2.32) (2.07) (1.87) (1.73) (1.61) (1.50) (1.42) (1.25) (1.13) (1.05) (0.99)

 

 

3/4 0.824 360 250 200 170 151 138 125 118 110 103  93  84  77  72

   

 

(10.2) (7.08) (5.66) (4.81) (4.28) (3.91) (3.54) (3.34) (3.11) (2.92) (2.63) (2.38) (2.18) (2.04)

 

1  1.049 680 465 375 320 285 260 240 220 205 195 175 160 145 135

   

 

(19.3) (13.2) (10.6) (9.06) (8.07) (7.36) (6.80) (6.23) (5.80) (5.52) (4.96) (4.53) (4.11) (3.82)

 

1/4 

1.380 

1400 950 770 660 580 530 490 460 430 400 360 325 300 280

   

 

(39.6) (26.9) (21.8) (18.7) (16.4) (15.0) (13.9) (13.0) (12.2) (11.3) (10.2) (9.20) (8.50) (7.93)

 

1/2 

1.610 

2100 

1460 

1180 990 900 810 750 690 650 620 550 500 460 430

   

 

(59.5) (41.3) (33.4) (28.0) (25.5) (22.9) (21.2) (19.5) (18.4) (17.6) (15.6) (14.2) (13.0) (12.2)

 2  2.067 3950 2750 2200 1900 1680 1520 1400 1300 1220 1150 1020  950  850  800
   

 

(112)  (77.9) (62.3) (53.8) (47.6) (43.0) (39.6) (36.8) (34.5) (32.6) (28.9) (26.9) (24.1) (22.7)

 

1/2 2.469 6300 4350 3520 3000 2650 2400 2250 2050 1950 1850 1650 1500 1370 1280

   

 

(178)  (123)  (99.7) (85.0) (75.0) (68.0) (63.7) (58.0) (55.2) (52.4) (46.7) (42.5) (38.8) (36.2)

 3  3.068 11000 7700 6250 5300 4750 4300 3900 3700 3450 3250 2950 2650 2450 2280
   

 

(311) (218) (177) (150) (135) (122) (110) (105) (97.7) (92.0) (83.5) (75.0) (69.4) (64.6)

 4  4.026 23000 

15800 

12800 

10900 9700 8800 8100 7500 7200 6700 6000 5500 5000 4600

   

 

(651) (447) (362) (309) (275) (249) (229) (212) (204) (190) (170) (156) (142) (130)

GAS SUPPLY PIPING

7

Table 3 - Gas Pipe Size

1.  Determine the required Cu. Ft. / Hr. by dividing the rated heater input by 1000. For SI / Metric measurements: Convert unit Btu. / Hr. to 
kilowatts. Multiply the units input (kW) by 0.0965 to determine Cubic Meters / Hour.    2.  FOR NATURAL GAS: Select the pipe size directly 
from the table.    3.  FOR PROPANE GAS: Multiply the Cu. Ft. / Hr. (Cubic Meters per Hour) value by 0.633; then use the table.    4.  Refer to 
the metric conversion factors listed in General Safety section for more SI unit measurements/conversions.

 To avoid equipment damage or possible personal injury, do not connect gas piping 

to this unit until a supply line pressure/leak test has been completed. Connecting the unit before 
completing the pressure/leak test may damage the unit gas valve and result in a fi re hazard.

 Do not rely on a shut off valve to isolate the unit while conducting gas pressure/leak 

tests. These valves may not be completely shut off, exposing the unit gas valve to excessive pressure 
and damage.

NOTICE: If more than one gas unit heater is to be 
served by the same piping arrangement, the total 
cubic feet per hour input and length of pipe must be 
considered.

NOTICE: If the gas unit heater is to be fi red with LP 
gas, see Table 3 or consult the local LP gas dealer 
for pipe size information.

NOTICE: HEATER INSTALLATION FOR USE WITH 
PROPANE (BOTTLED) GAS MUST BE MADE BY A 
QUALIFIED L.P. GAS DEALER OR INSTALLER. HE 
WILL ENSURE THAT PROPER JOINT COMPOUNDS 
ARE USED FOR MAKING PIPE CONNECTIONS; 
THAT AIR IS PURGED FROM LINES; THAT A 
THOROUGH TEST IS MADE FOR LEAKS BEFORE 
OPERATING HEATER; AND THAT IT IS PROPERLY 
CONNECTED TO PROPANE GAS SUPPLY SYSTEM.

Before any connection is made to an existing line             
supplying other gas appliances, contact the local gas 
company to make certain that the existing line is of 
adequate size to handle the combined load.

PIPE SIZING

To provide adequate gas pressure at the gas unit           
heater, size the gas piping as follows:
1.  Find the cu ft/hr by using the following formula:
                               Input

 

Cu ft/hr =

                         Btu per Cu ft
2.  Refer to Table 3. Match “Pipe Run in Feet” with            

appropriate “Gas Input - Cu Ft/Hr” fi gure. This fi gure 
can then be matched to the pipe size at the end of 
the column.

Example: It is determined that a 67 foot (20.4m) run of 
gas pipe is required to connect a 200 MBTU gas unit 
heater to a 1,000 Btu/cu. ft (0.29 kW) natural gas supply.

200,000 Btu/hr

                              = 200 Cu ft/hr
 1,000 Btu/cu ft

Using Table 3, a 1 inch pipe is needed.

NOTICE: See General Safety Information section for  
English/SI (metric) unit conversion factors.

Содержание QVEF 100 M

Страница 1: ...instructions to avoid exposure to fuel substances or substances from incomplete combustion which can cause death or serious illness The state of California has determined that these substances may ca...

Страница 2: ...have any questions after reading this manual contact the manufacturer See Identification of Parts Section for unit components Front View Rear View Indicates an imminently hazardous situation which if...

Страница 3: ...ied individual per instructions in this manual Also follow procedures listed on the Gas Equipment Start Up Sheet located in this manual 3 GENERAL SAFETY INFORMATION 1 foot 0 305 m 1 inch 25 4 mm 1 psi...

Страница 4: ...9 0 186 0 249 0 249 Motor Type SP SP PSC PSC PSC PSC PSC PSC PSC PSC R P M 1 050 1 050 1 140 1 140 1 140 1 140 1 140 1 140 1 140 1 140 Amps 115V 2 6 4 2 4 7 5 8 5 8 5 8 5 8 9 4 11 6 11 6 DIMENSIONAL D...

Страница 5: ...must not be installed in locations where air for combustion would contain chlorinated halogenated or acidic vapors If located in such an environment premature failure of the unit will occur Since the...

Страница 6: ...e between walls and the vertical sides of the Unit Heater shall be no less than 18 inches 457mm A minimum clearance of 6 inches 152mm must be maintained between the top of the Unit Heater and the ceil...

Страница 7: ...tiply the Cu Ft Hr Cubic Meters per Hour value by 0 633 then use the table 4 Refer to the metric conversion factors listed in General Safety section for more SI unit measurements conversions To avoid...

Страница 8: ...ing should be sized in accordance with the latest edition of ANSI Standard Z223 1 National Fuel Gas Code in Canada according to CSA B149 See Tables 1 and 3 for correct gas supply piping size If gas pr...

Страница 9: ...ersonal injury or death Standard units are shipped for use on 115 volt 60 hertz single phase electric power The motor nameplate and electrical rating on the transformer should be checked before energi...

Страница 10: ...regarding these venting conditions CARBON MONOXIDE Your venting system must not be blocked by any snow snow drifts or any foreign matter Inspect your venting system to ensure adequate ventilation exi...

Страница 11: ...llow this procedure 1 Hold power venter motor in position 2 Remove the three Phillips head screws from the motor adaptor plate 3 Remove the three screws which connect the power venter stack to the pow...

Страница 12: ...12 Figure 10A VENTING continued Figure 10B...

Страница 13: ...13 Figure 10C VENTING continued Figure 10D...

Страница 14: ...isting of a power venter motor and blower pressure switch and sealed flue collector in place of the conventional draft diverter The addition of external draft hoods or power ventors is not permitted A...

Страница 15: ...ywell Pilot Burner 13 High Limit This safety device is located on the rear header plate of the heat exchanger air inlet side 15 13 Figure 11 Burner Components Intermittent Pilot Ignition Also refer to...

Страница 16: ...C 0 9 kPa Adjustment of the pressure regulator is not normally necessary since it is preset at the factory However field adjustment may be made as follows a Attach manometer at pressure tap plug adja...

Страница 17: ...e minimum clearance requirements listed in this manual Under no circumstances should combustible material be located within the clearances specified in this manual Failure to provide proper clearance...

Страница 18: ...efer to Installation 7 Refer to Installation 1 Open all manual gas valves 2 Replace fuse or turn on power supply 3 Turn up thermostat 4 Check limit switch with continuity tester If open replace limit...

Страница 19: ...Do not ream 6 Refer to Operation 7 Check thermocouple connection and replace if defective 8 Eliminate drafts Refer to Installation 9 Inspect and correct all wiring 10 Inspect and correct ignition sys...

Страница 20: ...or short such as staples piercing thermostat wiring and correct Replace gas valve Refer to Operation 1 Be sure fan switch heater terminals are connected per diagrams 1 Refer to Operation 2 Check motor...

Страница 21: ...valve if not replace S8600 Igniter 1 Lengthen vertical run of flue pipe see venting 2 Burner orifice may be too large verify replace if req d 3 Increase air flow check fan size Check for proper voltag...

Страница 22: ...ROPELLER UNIT HEATERS Figure 13 Propeller Parts 1 HEAT EXCHANGER 2 FLUE COLLECTOR 3 BURNER DRAWER Figure 15 Internal Furnace Components Figure 16 Burner Assy Parts 115 1 60 MOTOR FAN GUARD FAN BLADE H...

Страница 23: ...400 units 6 dia flue outlet Increaser required To be supplied by manufacturer 23 REF NO DESCRIPTION 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wheel 7 Mounti...

Страница 24: ...rews Item 12 Do not loose these parts Using caution the motor will disengage from the Mounting Adapter Plate along with the Relay Junction Box and Pressure Switch Mounting Brackets will also disengage...

Страница 25: ...instructions or has been altered or modified in any way by any unauthorized person b to any expenses including labor or material incurred during removal or reinstallation of the Product c to any damag...

Страница 26: ...NOTES 26...

Страница 27: ...een installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GEN...

Страница 28: ......

Отзывы: