Table 1 - Performance and Dimensional Data - Tubular Propeller Unit Heater
Unit
Size
100 125 150 175 200 250 300 350 400
PERFORMANCE DATA†
Input
-
BTU/Hr.
100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
(kW)
(29.3)
(36.6)
(43.9)
(51.2)
(58.6)
(73.2)
(87.8)
(102.5)
(117.1)
Output
-
BTU/Hr.
81,000 101,250 121,500 141,750 162,000 202,500 243,000 283,500 324,000
(kW)
(23.7)
(29.6)
(35.6)
(41.5)
(47.5)
(59.3)
(71.2)
(83.0)
(95.0)
Thermal
Effi
ciency
(%) 81 81 81 81 81 81 81 81 81
Free
Air
Delivery
-
CFM
1,600 2,200 2,400 2,850 3,200 3,450 5,000 5,600 5,800
(cu. m/s)
(0.756)
(1.039)
(1.133)
(1.346)
(1.511)
(1.629)
(2.361)
(2.644)
(2.738)
Air
Temperature
Rise
-
Deg.
F
47 42 47 46 47 54 45 47 51
(Deg. C)
(26)
(23)
(26)
(26)
(26)
(30)
(24)
(26)
(28)
Full Load Amps at 120V
5.3
5.8
5.8
8.0
8.0
8.0
11.3
13.5
13.5
MOTOR DATA:
Motor HP (Qty.)
1/10
1/4
1/4
1/3
1/3
1/3
(2) 1/4
(2) 1/3
(2) 1/3
Motor kW
(0.080)
(0.19)
(0.19)
(0.25)
(0.25)
(0.25)
(0.19)
(0.25)
(0.25)
Motor Type
SP
PSC
PSC
PSC
PSC
PSC
PSC
PSC
PSC
R.P.M.
1,050
1,140
1,140
1,140
1,140
1,140
1,140
1,140
1,140
Amps @ 115V
4.2
4.7
4.7
5.8
5.8
5.8
9.4
11.6
11.6
DIMENSIONAL DATA - inches (mm)
“A” Overall Height to Top of Flue 33-3/4
33-3/4
33-3/4
33-3/4
33-3/4
33-3/4
34
34
34
(857) (857) (857) (857) (857) (857) (864) (864) (864)
“B”
Jacket
Width
of
Unit
20-3/4 20-3/4 20-3/4 32-3/4 32-3/4 32-3/4 50-3/4 50-3/4 50-3/4
(527) (527) (527) (831) (831) (831) (1289)
(1289)
(1289)
“C”
Width
to
CL
Flue
13-3/8 13-3/8 13-3/8 19-3/8 19-3/8 19-3/8 28-3/8 28-3/8 28-3/8
(340) (340) (340) (492) (492) (492) (721) (721) (721)
“D” Depth to Rear of Housing
11
11
11
11
11
11
12-1/4
12-1/4
12-1/4
(279) (279) (279) (279) (279) (279) (311) (311) (311)
“E”
Hanging
Distance
Width
18-5/8 18-5/8 18-5/8 30-5/8 30-5/8 30-5/8 48-5/8 48-5/8 48-5/8
(473) (473) (473) (778) (778) (778) (1235)
(1235)
(1235)
“F”
Discharge
Opening
Width
18-3/4 18-3/4 18-3/4 30-3/4 30-3/4 30-3/4 48-3/4 48-3/4 48-3/4
(476) (476) (476) (781) (781) (781) (1238)
(1238)
(1238)
“G”
Depth
to
CL
Flue
4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 4-3/4 5-1/8 5-1/8 5-1/8
(121) (121) (121) (121) (121) (121) (130) (130) (130)
“H”
Discharge
Opening
Height
24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2 24-1/2
(622) (622) (622) (622) (622) (622) (622) (622) (622)
“L”
Overall
Unit
Width
25-1/4 25-1/4 25-1/4 37-1/4 37-1/4 37-1/4 55-1/4 55-1/4 55-1/4
(641) (641) (641) (946) (946) (946) (1403)
(1403)
(1403)
*Flue
Size
Diameter
-
in.
5 5 5 5 5 5 6 6 6
(Dia.-mm)
(127)
(127)
(127)
(127)
(127)
(127)
(152)
(152)
(152)
Fan Diameter - in. (Qty.)
16
16
16
18
18
18
(2) 16
(2) 18
(2) 18
Gas
Inlet-Natural
Gas
(in.)
1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4
Gas Inlet- LP Gas (in.)
1/2
1/2
1/2
1/2
1/2
1/2 OR 3/4
1/2 OR 3/4
1/2 OR 3/4
1/2 OR 3/4
Approximate
Unit
Weight
-
lbs.
133 145 155 191 201 211 307 321 335
(kg)
(60)
(66)
(70)
(87)
(91)
(96)
(139)
(145)
(152)
Approximate
Ship
Weight
-
lbs.
173 185 195 241 251 261 367 381 395
(kg)
(78)
(84)
(88)
(109)
(114)
(118)
(166)
(173)
(179)
DIMENSIONS .XXX STANDARD UNITS
DIMENSIONS IN PARENTHESIS (XXX) MILLIMETERS
Figure 2 - Dimensional Drawing – Tubular Propeller Unit Heater
* For all installations, the
fl
ue collar is included with the unit and should be
fi
eld installed per the instructions included with the unit.
† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be derated 4% for each 1,000 ft. (305m) above sea level; refer to
local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).
For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be derated to 90% of the normal altitude rating,
and be so marked in accordance with the ETL certi
fi
cation.
D4617