Sterling GF-150 Скачать руководство пользователя страница 20

20

  1. Burner orifi ce too small.

 1. 

Irregular orifi ce causing whistle or resonance.

  2. Excessive gas input.

  1. Clogged main burners.
 2. 

Misaligned 

orifi 

ces.

  3. Insuffi cient combustion air.
  4. Possibly over fi red.

 1. 

Blocked 

venting.

  2. Insuffi cient combustion air.
  3. Blocked heat exchanger.
  4. Air leak into combustion chamber 

or draft hood.

 1. 

Shut off gas supply immediately! 

  2. Leaking gas test port on valve.
  3. Blocked heat exchanger.
  4. Blocked draft hood.
  5. Negative pressure in the building.

 1. 

Improper 

ground.

  2. Bad or broken spark cable.
 3. 

Faulty 

control.

  4. Pressure regulator set too low.

  5. Main burner orifi ces dirty.
 6. 

Improper 

venting.

  1. Gas supply is off.
  2. No power supply to unit.

  3. Thermostat not calling.

  4. Defective high limit.

  5. Defective drafter prove switch.

 6. 

Loose 

wiring.

 7. 

Improper 

ground.

  8. Improper thermostat or transformer wiring.
 

 

 1. 

Improper 

venting. 

  2. Unit under fi red.

  3. Building too cold.

Table 6 - Tubular Propeller Troubleshooting Guide

 1. 

Check with local gas supplier for proper orifi ce 
size and replace. Refer to “Operation”.

 1. 

Replace 

orifi 

ce. 

  2. Test and reset manifold pressure.

  1. Clean main burner ports.
  2. Replace manifold assembly.
  3. Insuffi cient combustion air.
  4. Check gas input and manifold pressures.

  1. Clean Flue. Refer to “Installation”.
  2. Clean combustion air inlet openings.
  3. Clean heat exchanger. Refer to “Installation”. 
  4. Determine cause and repair accordingly.

  1. Inspect all gas piping and repair.
  2. Check to ensure gas test ports are seated.
  3. Clean heat exchanger/fl ue.
  4. Clean fl ue collector. 
 5. 

See 

“Installation”.

  1. Check grounding wires and spark bracket 

connections.

  2. Inspect spark cable connections and cuts.
  3. Check to ensure spark is energized after 

pre purge period.

  4. Test and reset manifold pressure refer to 

“Operations”.

  5. Clean or replace orifi ces.
 6. 

Refer 

to 

“Installation”.

  1. Open all manual valves 

“check for leaks”

.

  2. Turn on power supply, check fuses and 

replace if bad.

  3. Turn up thermostat, Check for 24v on 

terminals R and W1 on terminal strip.

  4. Check switch for continuity if open with no 

heat present, replace.

  5. Check switch operation to ensure 

switch closes after draftor purge period. 
If it does not make/check tubing 
connections/ blockage.

  6. Check all wiring per diagram.
  7. Check all ground wires and connections.
  8. Check both, for wiring according to diagram;
 

 check for 24V at gas valve terminals during 

trial for ignition period if present and valve 
does not open. Replace valve.

 1. 

Refer 

to 

“Installation, 

Venting”.

  2. Check gas supply pressures to unit. Refer 

to “Installation”.

 3. 

Refer 

to 

“Installation”.

  A. Flame pops back.

 B. 

Noisy 

Flame.

  C. Yellow tip fl ame (some yellow 

tipping on LP gas is permissible).

 D. 

Floating 

fl 

ame.

 
 E. 

Gas 

odor.

 F. 

Delayed 

ignition.

  G. Failure to ignite.

 H. 

Condensation.

SYMPTOMS

POSSIBLE CAUSE(S)

CORRECTIVE ACTION

Содержание GF-150

Страница 1: ...en test fired and inspected It has been shipped free from defects from our factory However shipment and installation problems such as loose wires leaks or loose fasteners may occur It is the installer...

Страница 2: ...bustion Air 5 6 Proper Clearances 5 6 Suspension of Units 5 6 Gas Piping 7 8 ELECTRICAL CONNECTIONS 9 10 11 VENTING 12 13 14 15 16 OPERATION Explanation of Controls and Operation 17 Main Burner Orific...

Страница 3: ...t Start Up Sheet located in this manual Use only the fuel for which the heater is designed see rating plate Using LP gas in a heater that requires natural gas or vice versa will create risk of gas lea...

Страница 4: ...30 5 8 30 5 8 48 5 8 48 5 8 48 5 8 473 473 473 778 778 778 1235 1235 1235 F Discharge Opening Width 18 3 4 18 3 4 18 3 4 30 3 4 30 3 4 30 3 4 48 3 4 48 3 4 48 3 4 476 476 476 781 781 781 1238 1238 12...

Страница 5: ...st be equipped with an OSHA approved fan guard Refer to the latest edition of NFPA 88A Parking structures In Canada installation must be in accordance to the latest edition of CGA B149 Installation Co...

Страница 6: ...cent materials Make certain that the lifting methods used to lift the heater and the method of suspension used in the field installation of the heater are capable of uniformly supporting the weight of...

Страница 7: ...ity Gas Nominal Iron Internal Length of Pipe Feet meters Pipe Size Dia 10 20 30 40 50 60 70 80 90 100 125 150 175 200 in in 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622...

Страница 8: ...Code in Canada according to CGA B149 See Tables 1 3 for correct gas piping size If gas pressure is excessive on natural gas applications install a pressure regulating valve in the line upstream from t...

Страница 9: ...re air Always refer to the thermostat instructions as well as our unit wiring diagram and wire accordingly Avoid mounting the thermostat in the following locations 1 Cold Areas Outside walls or areas...

Страница 10: ...10 ELECTRICAL CONNECTIONS continued Figure 5d Tubular Units Equipped with Natural Gas and Propane LP Gas...

Страница 11: ...11 ELECTRICAL CONNECTIONS continued Figure 5e Tubular Unit Sizes with Optional 2 Stage Ignition...

Страница 12: ...its in areas under negative pressure due to large exhaust fans or air conditioning When required a flue vent fan should be installed in accordance with the instructions included with the fan 10 Vent c...

Страница 13: ...et Adjacent public walkways 7 feet above grade The venting system for these appliances shall terminate at least 4 feet 1 2m below 4 feet 1 2m horizontal from or 1 foot 0 3m above any door window or gr...

Страница 14: ...odes or in the absence of local codes with current CGA B149 1 Installation Codes for Natural Gas Burning Appliances and Equipment or CGA B149 2 Installation Codes for Propane Gas Burning Appliances an...

Страница 15: ...15 Figure 8A Figure 8B VENTING continued...

Страница 16: ...16 VENTING continued Figure 9A Figure 9B...

Страница 17: ...e period ends the power venter motor is de energized 6 The fan operation is delayed 30 seconds once the thermostat is closed and continues operation for 30 seconds after the thermostat opens NOTICE Th...

Страница 18: ...unit heaters must be orificed to 90 of the normal altitude rating and be so marked in accordance with ETL certification Check the gas input rate as follows Refer to General Safety Information section...

Страница 19: ...ssure altitude of the unit installation and the technician s name and date on the label using a permanent marker Refer to Installation Instruction section on Adjustments Gas Input Rate for adjusting t...

Страница 20: ...t openings 3 Clean heat exchanger Refer to Installation 4 Determine cause and repair accordingly 1 Inspect all gas piping and repair 2 Check to ensure gas test ports are seated 3 Clean heat exchanger...

Страница 21: ...tat 1 Replace or tighten 2 Clean power ventor wheel 3 Realign power ventor wheel 1 Check and tighten wires on fan circuit 2 Test for 115v on terminal ACB Heat and L2 if voltage is present replace moto...

Страница 22: ...heat If not present and all checks are normal replace 1 Check power ventor circuit per wiring diagram 2 Check motor voltage and amp draw to motor name plate replace if motor found defective 3 Check f...

Страница 23: ...er 3 5 Amp fuse on circuit board 1 Common side of transformer grounded to chassis 2 Loose spark ignitor 1 Gas supply off or gas supply pressure too low 2 Flame sense rod contaminated or loose wire 3 G...

Страница 24: ...l safety devices supplied with your unit NOTICE The heater and vent system should be checked once a year by a qualified technician All Maintenance Service information should be recorded accordingly on...

Страница 25: ...ogenated hydrocarbons precipitated in the air d to any workmanship of the installer of the Product 3 This limited warranty is conditional upon a advising the installing contractor who in turn notify t...

Страница 26: ...ICATION OF PARTS PROPELLER UNIT HEATERS Figure 13 Heat Exchanger Assembly Figure 14 Electrical Control Panel Figure 11 Propeller Parts Figure 12 Component Parts D4430 Fan Guard Fan Blade Hardware Hard...

Страница 27: ...er Assembly 300 400 Unit Sizes Shown HOW TO ORDER REPLACEMENT PARTS Please send the following information to your local representative if further assistance is needed contact the manufacturer s custom...

Страница 28: ...n installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equipment unless you fully understand the controls GAS EQUIPMENT START UP GENER...

Отзывы: