Sterling Power BB122430 Скачать руководство пользователя страница 6

Sterling Power Products

Copyright 

Engine Starter 

Battery

(connected to alternator)

 

Important

NEGATIVES

should all be common.

DON'T USE CHASSIS

We recommend joining

the BB’s neg. to the 

starter battery negative.

For improved efficiency.

House / Domestic / Aux

Battery Bank

(arranged here as a 12V bank)

 

 

Temperature Sensor 
(TSAY)  optional  fit. 
Polarity of wires into 
(1) and (2) does NOT 
matter.

 Installation Diagram / all non Solar Models

BMS (1)

BMS (2)

Use  BMS  1

  -  if  your  BMS  trips  and  provides  a  0V 

(ground signal), then use BMS 1. This shall result in the 
BB turning off. Once the BMS removes this trip status, 
i.e. the 0V signal goes back to a +ve signal, the BB shall 
start charging again. 

Use BMS 2

 - if your BMS trips to a +ve voltage (2V-17V), then 

use BMS 2. This shall result in the BB turning off when this 
voltage is received. Once the BMS removes this trip status, 
i.e. the +ve signal goes back to 0V signal, the BB shall start 
charging again. 

BMS 1
status:
operational: 2-17V
trip voltage: 0V

BMS 2
status:
operational: 0V
trip voltage: 2V-17V

line to ignition

(recommended if vehicle is Euro 6)

Aux

Batt

out +

Engine

Batt. 

input +

     Com.

      Neg.

BMS 2 (5)

BMS 1 (6)

Battery temp. 
sensor (1,2)

Ignition
feed (4) 

Upper
   Lower

Remote 

control

+

-

1   2   3

4  5  6 

f u s e 

+

    5  6 

fuse

fuse

6

BMS and remote features appear later

Temperature sensor cables are not polarity sensitive, install either way. If you wish to install, connect the temp 
sensor to the negative of the domestic / aux. batteries. 

When  temperature  sensor  senses  the  temperature  lower  than  20Deg  C  the  voltage  shall  go  up  on  the 
charger’s output and when the temperature is higher than 20Deg C the charge voltage shall drop. The rate is 
18mV (0.018V) per Deg C or  0.018V /  Deg C. If sensor temperature is at 10 Deg C the voltage elevation shall 
be 0.018 x 10 = 0.18V. This shall explain why, in cooler climates / seasons you may see slightly elevated charge 
voltage / voltage at your batteries. This is no concern. In warmer climates / seasons you shall see slightly lower 
charge voltages. This voltage fluctuation is only with ‘lead acid style’ batteries. For lithium profiles, there is no 
voltage fluctuation.  

The temperature sensor shall trip the charger if the temperature at the battery >55DegC.

If the BB is in either lithium profiles the unit shall trip at 0DegC, if temp sensor is connected. This temperature 
can be adjusted. If you do not want the 0DegC trip or any trip, please uninstall the temperature sensor.  

remote voltage sense
compensates for
potentially long cable
runs to domestic 
battery. 

 BMS connectors

 Temperature sensor (part no. TSAY)

These BMS connectors can also be used as simple on/off signal connectors. If you wish for the BB to turn off with a live (+ve) signal 
please use BMS 2. If you wish for the BB to turn off based on a ground (0V) signal, use BMS 1. These signals do not have to come 
from a BMS, they can come from any source. 

Fuse ratings 
on Page 5

fuse

 Remote voltage sense

The remote voltage sense is designed to achieve the correct charge voltage at the charging battery (house) itself. 
There is often voltage drop across DC cabling, this sense feeds back to the BB what the charge voltage at the BB 
should be in order to get the correct charge voltage at the battery. The sense cable, itself, carries no current, it can 
be as thin as you can find. Please connect between (3) and the positive terminal of output battery. 

Содержание BB122430

Страница 1: ...s BBS1230 model only voltage should not exceed 31V 12V panel The BB by default shall start charging when the starter input voltage exceeds 13 5V and switches off when the voltage drops below 13 3V all...

Страница 2: ...ging battery profile type Front Panel Display I Page 4 First and second LED column meter readings Front Label display annotated Guide to the 2 buttons Page 11 What the LEDs mean Simplified chart corre...

Страница 3: ...rrent limiting With fuses protecting the DC cables In a well ventilated dry dust free and condensation free environment When instruction manual has been read through Safety Symbols Example WARNING Nev...

Страница 4: ...fl BMST S No Fault S P Pack fl Regen timer off S on fl Batt Sense on S Volt drop sense fl 1 2 power S night fl Low Volt in fl out S High bat temp fl TCO S Output Voltage 11 10 9 8 7 6 5 4 3 16 17 18 1...

Страница 5: ...12 13 10 8 9 3 4 15 16 5 7 15 Solar positive input from 12V solar panel up to 31V 16 Solar negative input from 12V solar panel up to 31V Models BBS1230 This chart is a guideline based on the typical...

Страница 6: ...her than 20Deg C the charge voltage shall drop The rate is 18mV 0 018V per Deg C or 0 018V Deg C If sensor temperature is at 10 Deg C the voltage elevation shall be 0 018 x 10 0 18V This shall explain...

Страница 7: ...egative Common Negative BMS 2 BMS 1 Ignition feed Remote Voltage sense Upper Lower Remote control Solar Pos lithium BMS Controller if used fuse fuse 50A 50A Sterling Power Products H Charge Float In U...

Страница 8: ...through the custom charge profiles as appears on page 15 If you do not want this feature at all please remove the temperature sensor from the connector on the BB This shall immediately engage the BB t...

Страница 9: ...go The unit shall now ONLY operate when there is a live ignition feed if the BB is wired up without an ignition the unit shall simply not function This shall limit the unit s flexibility However this...

Страница 10: ...or lower if in warm climate than the preconceived voltage The voltage requirements of the battery company will override our recommendations as it is them who are supporting the battery warranty Chang...

Страница 11: ...re 10 Force to float 15 Night Mode 20 1 2 Power Mode 25 Standby 30 Turn unit off on again 40 OEM Lock 45 Solar Charger on off 50 BB Charger on off SELECT SETUP ENTER Guide to the buttons For a more de...

Страница 12: ...off Within this timer window the ECU on board should prompt the alternator to turn on again as the ECU is monitoring the starter battery s depletion When the alternator turns on again the voltage sho...

Страница 13: ...power after these 8 hours You have to repeat this procedure every time you need it Turn the charger to standby If you wish to put your BB into standby then apply this mode Standby is a one off setting...

Страница 14: ...column of LEDs shall flash Press the setup select button to move LED down to custom Hold both buttons for 2 seconds to confirm Opportunity to adjust Fast Charge Bulk Absorption voltage Red Custom LED...

Страница 15: ...ED column to refer to the brown scale 0 960 select the correct time Once content wait 30 seconds or press both buttons to confirm A from the middle of each row will green LED flash for around 8 second...

Страница 16: ...e display shall read loc on number you have stored To remove loc return to loc and re enter the number Press select button and the display should read loc off green back light Please make a note of th...

Страница 17: ...arger DIGITAL control SELECT 15 4V 15 0V 14 6V 14 2V 13 8V 13 4V 13 0V 12 6V 12 2V SETUP ENTER www sterling power usa com www sterling power com Designed and Developed in England Made in Taiwan 15 4V...

Страница 18: ...requires increase rpm of engine possible belt slip Or your alternator current rating is lower than the rating of the BB Possibly set BB to half power mode You need a larger alternator Is your output...

Страница 19: ...does not apply for shipping organised by yourself Please do not throw out any shipping or packaging materials All returns for any reason will require a proof of purchase with the purchase date The pr...

Отзывы: