Thank you for purchasing the Sterling Automatic AC Crossover Switch, a sophisticated product which will help 
you to safely and comfortably switch your 

 power sources on board. 

M

AIN

 P

RODUCT

 F

EATURES

The Sterling Automatic AC Crossover Switch is a three-stage sequential switch which will automatically switch 
the AC power sources on board. It will ensure that only one AC power source will be on your boat’s ring mains 
at any one time, thereby protecting your electrical equipment from possible damage.

The complexity of the system is masked by its easy installation and fully automatic operation. Basically, the unit 
is a three-stage sequential switch with the channel marked “shore power” as the priority selection. The channel 
marked “generator” is second, and the channel marked “inverter” is third. This default setting works on the 
assumption that the boat has shore power, a generator and an inverter. However, some boats may have 2 
generators and no inverters, in which case you can simply use the inverter port as another generator port etc. In 
fact, you can mix and match as you wish. There are a few things which are unique to each channel but these do 
not affect the channels from being used for an input source other than the default.

It is important to stress that this system operates by itself in fully automatic mode and requires no human 
intervention. However, for more complicated systems, the Sterling Automatic AC Crossover Switch offers many 
additional and sophisticated features.

I

NSTALLATION (see Fig. 1)

Cable Connections

System Components

 This channel has a 10-

second delay in order to allow the generator to fire up and to reduce the high voltage surge associated with 
generator startups. (All other channels work on about a 1 second delay.)

AC

Remove the screws from each end of the unit to remove the end caps. The p.c.b. can slide about 1 - 2 inches 
either way to expose the screw connectors for installing the cable. Slide the cables through the slots in the end 
caps (If required, you can make the openings slightly bigger.). For 32A three-core cable, the outer cable sheath 
will need to be removed to enable the smaller internal insulated cables to be worked on with ease.

Connect cables as per drawing. Run the wires through the cable ties. When the wiring is completed, the cable ties 
can be pulled tight to lock and fix the wiring. Replace the end caps.

Before starting to install the unit, 

please read and understand these instructions completely, in order to avoid any possible safety risks and to 
avoid any danger of damaging the unit or your boat / vehicle.

All high voltage input and output connections must be totally isolated before working on the circuits or 
this unit! It is strongly advised that any work being performed on high voltage equipment or circuits must 
be done by professionals only.

This unit comes set up as standard for use with either 110V or 230V, 40Hz - 60Hz with a current rating of 
32A. Each input channel is fused at 32A. For safety, the internal relay control system is rated at 40A 
continuous.

Install the unit as per wiring diagram. Ensure that the cables being used have the correct 
rating and size for the power being applied. Fit in a cool, dry and well ventilated place.

 

 

This channel 

is the only channel with reverse polarity warning.

 

 

Shore power input:

 

Generator input:

Connect live to L and neutral to N on the screw terminals. The fuse beside the connection 

block is a 32 amp fuse. In the event of this fuse blowing, simply replace it and check why the rating of the 
equipment was exceeded. Please ensure that adequate cable is used to cover the usage on the boat. 

 Connect live to L and neutral to N on the screw terminals.  The power source does not 

necessarily have to be a generator. It could also be an inverter or any other a/c power source; it is simply the next 
channel which the system will engage, when and if the shore power is disconnected.

A

B

2

 

 

  

 

 

 

  

This is a low power signal only and is not to be used as a power connection! 

AC

 

 

 

 : 

 

 

 

if

 

 

 

 

 Inverter / Generator Input:

A/C Ring Main Output:

Earth Connections:

Battery Charger Disengage Signal:

Onboard Consumer Unit A/C Distribution Board:

A/C Generator Input

Shore Power Input Socket: 

 Inverter: 

Zinc Saver / Galvanic Isolator: 

Remote Display:

 Connect live to L and neutral to N on the screw terminals. The power source 

does not necessarily have to be an inverter. It could also be a generator or any other a/c power source. It is simply 
the channel with the lowest priority. The inverter channel also controls a signal which can be used to isolate your 
battery charger when the inverter is on line. This is to prevent the inverter operating your charger which can lead 
to an ever decreasing power loop.

This is the main a/c output, and should be connected to an earth leakage detector of 

some form (R.C.D) and then to a fused distribution box.

 All the earth lines are connected to the same point, and this point should be grounded to 

the boat’s bonding system to comply with European and American regulations. 

This connection 

provides a signal to switch a relay which is connected to your battery charger’s a/c input, thus preventing the 
charger to work at the same time as the inverter.

 

 This should contain your main R.C.D. (earth leakage 

detector) and fuses for distributing the a/c power around the boat. Note that an R.C.D. is a requirement for any 
boat with a/c power on board! The Sterling automatic crossover switch is not an R.C.D.

The maximum current rating of the unit is 32A which is about 7kW at 230V or 3.5kW 

at 110V. Therefore,

Most European shore sockets are about 16A. The maximum current rating of the 

automatic crossover switch 32A, so there should not be any problems with most shore power supplies.

The maximum current rating of the unit is 32A which is about 7kW at 230V or 3.5kW at 110V. 

Therefore, 

The same applies if a 

second generator is used instead of an inverter.

Protects the boat from stray electric corrosion coming up the earth cable and 

destroying the zinc and other metals on the boat. For more information on this, please refer to our web site 
regarding this highly recommended product which is available from your local Sterling stockist.

 The remote display gives the following basic information:

Green light on:

 This shows the channel which is currently being used.

Green light flashing:

 Power is available on this channel, but it is not the power currently being used.

Red light

 

flashing:

 Fault on p.c.b. Either the relays have become defective, or a internal fuse has blown. It will 

not show which fuse, and it is up to you to test them, but it will most likely be the shore power fuse.

Red light on:

 This indicates reverse polarity on the shore power input. It is then up to you what you do about 

this. We strongly recommend you stop using the a/c shore power until such time as the marina or an electrician 
has fixed the problem.

The Sterling AC Automatic Crossover Switch comes with the ability to 

shut down the battery charger if it is on the boat’s ring mains. You may wish to use this feature because when the 
inverter is on line, you certainly do not want to run the battery charger from the inverter. 

In order to remove the need to remember to switch the battery charger off every time you start the inverter, you 
can use a suitable standard 230V (or 110V depending on your setup) relay available from your local electrical 
wholesaler. Connect the relay to your battery charger’s main feed. The relay energising circuit should then be fed 

directly to the AC crossover switch control circuit 

 

. The AC power control circuit is normally in the open 

position and closes when the inverter circuit is on line. So when the control circuit closes, it will energise your 

battery charger control relay 

 

 and thereby open the charger relay

.

Warning: 

Do not under any 

circumstances try to feed the main battery charger power directly into the control circuit on the 

 

crossover switch! The control must be done through a relay (contactor)!

 if you have a larger generator set, do not direct all the power through the switch!

 you have a larger inverter, do not direct all the power through the switch! 

C

D

E

F

F

O

G

H

I

J

K

L

3

Содержание AC32A

Страница 1: ...A STERLING POWER PRODUCTS Automatic 90V 260V AC 32A 3 way Crossover Switch English Deutsch technology 4 D UR L A A T B I L G E I D D E C I S M I G A N NYD ProDigital RoHS compliant www sterling power...

Страница 2: ...The p c b can slide about 1 2 inches either way to expose the screw connectors for installing the cable Slide the cables through the slots in the end caps If required you can make the openings slightl...

Страница 3: ...rrosion coming up the earth cable and destroying the zinc and other metals on the boat For more information on this please refer to our web site regarding this highly recommended product which is avai...

Страница 4: ...connected the wrong way round It usually refers to the extension cable from your boat to the shore supply However marinas or newly built boats are not immune from making the odd mistake here In the e...

Страница 5: ...5...

Страница 6: ...0V 260V AC 40Hz 60Hz max 32A K C B D J M S TERLING POWER PRODUCTS a c automatic crossover switch Shore power 1 Generator 2 Inverter 3 Fault green L E D flashing power available green L E D on circuit...

Страница 7: ...oller internal battery charger control connection circuit N L A N L N L relay contactor energising coil AC power from distribution ring main AC power to battery charger power contactor or relay contro...

Страница 8: ...lternative Zuordnung der Spannungsquellen Der Automatische Umschalter arbeitet unter normalen Umst nden vollautomatisch und erfordert keinen Benutzereingriff F r komplexere Systeme bietet das Ger t za...

Страница 9: ...bindung des Umschalters mit Ihrem 230V 110V Bordnetz Der Anschluss sollte ber einen geeigneten Fehlerstrom Schutzschalter FI und eine abgesicherte Bordnetz Verteilung erfolgen Alle Schutzleiter sind m...

Страница 10: ...sorgt wird Dies kann entweder manuell geschehen oder automatisch ber die integrierte Ladeger t Abschaltung des Automatischen Umschalters Siehe oben Dieses externe Relais dient der automatischen Abscha...

Страница 11: ...nergiespar Funktion der meisten Wechselrichter ben tig eine Mindeslast von ca 10W bis 20W um den Wechselrichter zu aktivieren Der Automatische Umschalter bietet jedoch nur eine Last von ca 2W was f r...

Страница 12: ...STERLING POWER PRODUCTS LTD Website www sterling power com Email help sterling power com Copyright 2006 by Sterling Power Products Ltd Copying and reprinting not allowed Changes and errors excepted...

Отзывы: