Shanghai STEP Electric Co., Ltd.
30
closes to position.
F31 = 1
~
30%, The inverter continues to close the door at the door-closing speed,
until there is a opening signal.
F32 T
orque boost
range
:
0-30
Inverter torque setting, compensating torque at lower frequency
(
less than10Hz
)
Note
:
F31 and F32 are set based on the holding torque and rated current of
motor. If lasting too long, motor may burn out.
F33
Speed of holding Torque of door closing and openning range
:
0-90
Set the speed when holding Torque of door closing and openning
;
Factory setting
is 60
,
Do not change it unless it is needed
F34 v/f
compensating torque at low speed range
:
0-30
compensating torque at low speed in mode v/f
Note
:
F4 is set based on the holding torque and rated current of motor. If it is
set too big , Noise of motor may occur,and if it is set too small, High speed can not
be pulled up.
F35 Set of solutuio for door-blocked
range
:
0/1/2/3/4/5
When door is blocked, inverter will work as following:
F35 = 0
:
stop output
,
closing door is forbidden
,
shield the closing instruction of
PC
F35 = 1
:
shield the closing instruction of PC for 3 seconds, then respond it
F35 = 2
:
shield the closing instruction of PC for 5 seconds, then respond it
F35 = 3
:
shield the closing instruction of PC for 10 seconds, then respond it
F35 = 4
:
shield the closing instruction of PC for 20 seconds, then respond it
F35 = 5
:
shield the closing and opening instruction of PC, then execute the
openningaction in reverse automatically
Note
:
inverter will respond the opening instruction of PC immediately
whatever F35 is.
F36 S
et input mode
range
:
00000000~11111111
Parameter F36 is binary
,
the 0
~
7 digit
and
input point INPUT0~INPUT7
correspond
,
setting 0
(
short upright
)
means NO input point
,
setting1
(
long upright
)
means NC input point.
Note
:
If the control mode of inverter is
V/F
,
Please set parameter F36 first.
For Type A1, parameters F36.0 ~ F36.2are available
,
others are void
For Type A2/A3, parameters F36.0 ~ F36.7are available
,
others are void