  Setup & Commissioning (continued)

Light level

The light level feature allows lighting to 

remain OFF during daylight, regardless of 

occupancy. Daytime operation is at 200 

footcandles (factory setting). Nighttime 

operation is at .2 footcandles. 

The adjusting screw turned fully clockwise 

means daylight operation at approx. 200 

fc (factory setting). Turning fully counter-

clockwise means nighttime operation at 

.2 fc. When adjusting the detection zone 

and for the performance test in daylight, 

the adjusting screw must be turned fully 

clockwise.

Time delay

Time delay is the period of time lights 

remain on after the last detection. 

Adjustment ranges from 30 sec (factory 

setting) to 30 min.

The adjusting screw turned fully counter-

clockwise means the shortest time and 

fully clockwise means the longest. The 

time delay is restarted by any movement 

detected before this time elapses. The 

shortest time setting is recommended 

when adjusting the detection zone and for 

the performance test. 

Note: Every time the light switches off, it 

takes approximately two seconds for the 

sensor to start detecting movement again. 

Reach/sensitivity

The sensor’s reach setting can be 

adjusted. Turning the adjustment screw 

fully counter-clockwise selects minimum 

reach (about 3.3 feet) and fully clockwise 

selects maximum reach (about 26 feet). 

Time delay:  30 seconds 
to 30 minutes

Light level: .2 (night) to 200 
(day) footcandles

Sensitivity (middle): adjusts 
coverage reach from approx 
3.3 feet to 26 feet

7

Coverage size 

The HFLUM2-120 coverage is 360° 

and its reach ranges from 3.3 to 26 

feet (see next page for reach/sensitivity 

adjustment). Actual coverage may vary 

depending on luminaire confi guration and 

environmental conditions.

Lamp seasoning

Some fl orescent lamp manufacturers 

recommend seasoning or “burning in” 

lamps. To meet this recommendation, the 

following seasoning procedure should be 

carried out for new fl uorescent lamps. 

•  Connect luminaire, switch ON for at 

least one minute

•  Switch power supply OFF/ON twice 

(main or light switch within 0.5 – 1 sec)

•  Alternatively, you can start the 

seasoning process by using the 

potentiometers. Turn all 3 setting 

controls fully clockwise, then turn 

the middle setting control (time) fully 

counter-clockwise and fully clockwise 

again (within 10 sec)

•  The seasoning process is confi rmed by 

switching the light OFF and back ON 

again twice

•  The light is now left ON for 100 hours 

without sensor function. Do not 

disconnect the light from the main 

power supply during this period.

•  The luminaire automatically returns to 

sensor mode after 96 hours

3.3 - 26 ft

1 - 8 m

3.3 - 13 ft

1 - 4 m

  Setup & Commissioning

6

Test mode

•  Ensure that the sensor is in test mode.

 

- set time delay to minimum setting of 

30 seconds

 

- set light level to maximum 

(“day” setting, light level function 

overridden)

 

- set sensitivity to minimum

•  Turn power ON at the circuit breaker 

(lights will turn ON). After a warm up 

period of up to one minute, lights will 

turn OFF if the sensor does not detect 

motion.

•  Walk in view of sensor, lights should turn 

ON. Be still for 30 seconds and lights 

should turn OFF. 

After setup and commissioning tests are 

complete, adjust the light level, time delay, 

and reach settings to fi t the application 

needs.

www.steinel.net   (800)  852-4343

www.steinel.net   (800)  852-4343

INST_HFLUM_newLayout_ENU-FRA.indd   8-9

INST_HFLUM_newLayout_ENU-FRA.indd   8-9

12.04.11   16:54

12.04.11   16:54

Содержание HFLUM2-120

Страница 1: ...W8J8303 IC 8529A 8303 Fran ais RoHS Compliant HFLUM2 120 110011483 04 2011 Technical changes subject to no prior noti cation STEINEL America Inc 9O51 Lyndale Avenue South USA Bloomington MN 55420 Tel...

Страница 2: ...lled and used in accordance with appropriate electrical codes and regulations Installation by a qualified electrician is recommended Voltage Load rating Transmitter power Power consumption Time delay...

Страница 3: ...lled and used in accordance with appropriate electrical codes and regulations Installation by a qualified electrician is recommended Voltage Load rating Transmitter power Power consumption Time delay...

Страница 4: ...ree terminals for streamlined wiring Use only solid 16 20 AWG CU wire Strip insulation 9 10mm 0 37 inch Operation The HFLUM2 120 operates by turning lights on automatically when occupancy is detected...

Страница 5: ...ree terminals for streamlined wiring Use only solid 16 20 AWG CU wire Strip insulation 9 10mm 0 37 inch Operation The HFLUM2 120 operates by turning lights on automatically when occupancy is detected...

Страница 6: ...ch sensitivity adjustment Actual coverage may vary depending on luminaire configuration and environmental conditions Lamp seasoning Some florescent lamp manufacturers recommend seasoning or burning in...

Страница 7: ...ch sensitivity adjustment Actual coverage may vary depending on luminaire configuration and environmental conditions Lamp seasoning Some florescent lamp manufacturers recommend seasoning or burning in...

Страница 8: ...the party responsible for compliance could void the user s authority to operate the equipment Malfunction Cause Remedy 9 Consid rations relatives l usage Lorsque des lampes uorescentes sont neuves ou...

Страница 9: ...the party responsible for compliance could void the user s authority to operate the equipment Malfunction Cause Remedy 9 Consid rations relatives l usage Lorsque des lampes uorescentes sont neuves ou...

Страница 10: ...1 2 3 4 5 2 1 3 4 5 Le HFLUM2 120 met des ondes lectromagn tiques hyper fr quence 5 8 GHz Tout mouvement dans la zone contr l e entra ne un changement de l cho qui se traduit par une d tection Les d...

Страница 11: ...1 2 3 4 5 2 1 3 4 5 Le HFLUM2 120 met des ondes lectromagn tiques hyper fr quence 5 8 GHz Tout mouvement dans la zone contr l e entra ne un changement de l cho qui se traduit par une d tection Les d...

Страница 12: ...d clairage dans l espace de 0 5 1 s titre d alternative vous pouvez d mar rer le processus de saisonnalisation en utilisant les potentiom tres Tourner les 3 commandes de r glage dans le sens des aigu...

Страница 13: ...d clairage dans l espace de 0 5 1 s titre d alternative vous pouvez d mar rer le processus de saisonnalisation en utilisant les potentiom tres Tourner les 3 commandes de r glage dans le sens des aigu...

Страница 14: ...ouverture d environ 3 3 pieds 1 m 26 pieds 8 m www steinel net 800 852 4343 Pas de courant au niveau du d tecteur Les lumi res ne s ALLUMENT pas Les lumi res ne s TEIGNENT pas Les lumi res s ALLUMENT...

Страница 15: ...ouverture d environ 3 3 pieds 1 m 26 pieds 8 m www steinel net 800 852 4343 Pas de courant au niveau du d tecteur Les lumi res ne s ALLUMENT pas Les lumi res ne s TEIGNENT pas Les lumi res s ALLUMENT...

Страница 16: ...W8J8303 IC 8529A 8303 Fran ais RoHS Compliant HFLUM2 120 110011483 04 2011 Technical changes subject to no prior noti cation STEINEL America Inc 9O51 Lyndale Avenue South USA Bloomington MN 55420 Tel...

Отзывы: