Setup & Commissioning (continued)
Light level
The light level feature allows lighting to
remain OFF during daylight, regardless of
occupancy. Daytime operation is at 200
footcandles (factory setting). Nighttime
operation is at .2 footcandles.
The adjusting screw turned fully clockwise
means daylight operation at approx. 200
fc (factory setting). Turning fully counter-
clockwise means nighttime operation at
.2 fc. When adjusting the detection zone
and for the performance test in daylight,
the adjusting screw must be turned fully
clockwise.
Time delay
Time delay is the period of time lights
remain on after the last detection.
Adjustment ranges from 30 sec (factory
setting) to 30 min.
The adjusting screw turned fully counter-
clockwise means the shortest time and
fully clockwise means the longest. The
time delay is restarted by any movement
detected before this time elapses. The
shortest time setting is recommended
when adjusting the detection zone and for
the performance test.
Note: Every time the light switches off, it
takes approximately two seconds for the
sensor to start detecting movement again.
Reach/sensitivity
The sensor’s reach setting can be
adjusted. Turning the adjustment screw
fully counter-clockwise selects minimum
reach (about 3.3 feet) and fully clockwise
selects maximum reach (about 26 feet).
Time delay: 30 seconds
to 30 minutes
Light level: .2 (night) to 200
(day) footcandles
Sensitivity (middle): adjusts
coverage reach from approx
3.3 feet to 26 feet
7
Coverage size
The HFLUM2-120 coverage is 360°
and its reach ranges from 3.3 to 26
feet (see next page for reach/sensitivity
adjustment). Actual coverage may vary
depending on luminaire confi guration and
environmental conditions.
Lamp seasoning
Some fl orescent lamp manufacturers
recommend seasoning or “burning in”
lamps. To meet this recommendation, the
following seasoning procedure should be
carried out for new fl uorescent lamps.
• Connect luminaire, switch ON for at
least one minute
• Switch power supply OFF/ON twice
(main or light switch within 0.5 – 1 sec)
• Alternatively, you can start the
seasoning process by using the
potentiometers. Turn all 3 setting
controls fully clockwise, then turn
the middle setting control (time) fully
counter-clockwise and fully clockwise
again (within 10 sec)
• The seasoning process is confi rmed by
switching the light OFF and back ON
again twice
• The light is now left ON for 100 hours
without sensor function. Do not
disconnect the light from the main
power supply during this period.
• The luminaire automatically returns to
sensor mode after 96 hours
3.3 - 26 ft
1 - 8 m
3.3 - 13 ft
1 - 4 m
Setup & Commissioning
6
Test mode
• Ensure that the sensor is in test mode.
- set time delay to minimum setting of
30 seconds
- set light level to maximum
(“day” setting, light level function
overridden)
- set sensitivity to minimum
• Turn power ON at the circuit breaker
(lights will turn ON). After a warm up
period of up to one minute, lights will
turn OFF if the sensor does not detect
motion.
• Walk in view of sensor, lights should turn
ON. Be still for 30 seconds and lights
should turn OFF.
After setup and commissioning tests are
complete, adjust the light level, time delay,
and reach settings to fi t the application
needs.
www.steinel.net (800) 852-4343
www.steinel.net (800) 852-4343
INST_HFLUM_newLayout_ENU-FRA.indd 8-9
INST_HFLUM_newLayout_ENU-FRA.indd 8-9
12.04.11 16:54
12.04.11 16:54