4.2 Connection
WARNING
Danger of explosion from sparking! Danger of electric shock!
X
The inverter may only be connected to the local consumer devices and the
battery by trained personnel and in accordance with the applicable regula-
tions.
X
Connections must always be made in the sequence described below.
X
The cables pre-fitted to the inverter must not be damaged.
4.2.1 AC output of the inverter
X
Connect the black 2-core cable to a circuit breaker of a distribution board
in accordance with the applicable regulations.
or
X
Mount a mains power socket on the black 2-core cable in accordance with
the country-specific regulations.
X
In case that due to the local prescriptions or the AC consumers a connec-
tion to ground is required:
Realize ground according to the adjacent figure (provided TN system is
permitted).
4.2.2 Connecting the battery to the inverter
WARNING
Danger of explosion from sparking! Danger of electric shock!
X
Before connecting the battery, ensure that no consumer devices are switched
on and the rotary switch is in the “Off” setting.
X
Ensure that the polarity of the battery connection is correct.
X
The cables pre-fitted to the inverter must not be extended.
X
Follow the instructions of the battery manufacturer.
X
Turn the rotary switch to the “Off” setting.
X
Ensure that the connection to the mains grid has been carried out correctly.
X
An easily accessible disconnection device should be connected to the
battery cables immediately next to the battery. The disconnection device
should consist of a DC circuit breaker or a DC fuse. Choose a circuit breaker
or fuse with a minimum voltage of 15 V/30 V/60 V for 12 V/24 V/48 V rated
voltage and a disconnection function of at least 150 A (PI 500-12/1100-24)
or 75 A (PI 550-24/1500-48) slow blow or 1,2 times the amount fast blow
% ##&''#&*&;#;<
X
Connect the red battery cable to the positive te of the battery.
X
Connect the black battery cable to the minus terminal – of the battery.
X
Ensure that the connections are tight.
The inverter is ready for operation.
R
L
N
PE
C
D
L
N
GND/PE