SYMPTOM
DISPLAY IS BLANK
DISPLAY SHOWS
DISPLAY SHOWS
‘
DP Err
’ IS DISPLAYED
‘
OP CAL
’ IS DISPLAYED
‘
IP CAL
’ IS DISPLAYED
POSSIBLE CAUSE
No power
Input is out of range
(above maximum)
Input is out of range
(below minimum)
The displayed value (excluding
total) is greater than 6 digits
(i.e. 999999)
The output pod has been corrupted
The input calibrated data has been
corrupted
ACTION
Check power supply connections
Check that the engineering high value is
correct
Check that the engineering low value is
correct
This can occur if the PV is configured
outside of the displayable range
Re-configure output. If the error is still
present replace the output pod
Re-input calibration data. If the error is
still present replace the unit