background image

Holding down the Cycle key whilst applying power to the unit will cause all settings to revert to factory
default.

USE THIS FUNCTION WITH CAUTION 

as there is no way of reversing it. 

NOTE 

that this function will also clear any TFML module loaded.  

The input submenu is where the input to the unit is
selected and configured.

Output configures the outputs of the unit. The format of
the output submenu varies according to the Output Pod
fitted. The two possible output types are:

1. Current transmission
2. Twin Relay

This submenu configures the units characteristics e.g.
communications and passcode.

If a TFML is loaded, this submenu gives access to the 8
TFML configuration registers.

tFnL

SyStEn

OUt  2

OUt  1

InPUt

FROM

RUN MODE

10.0 MENU MAP

11.0 RESETTING THE DEVICE

12.0 INPUT MENU STRUCTURE

Page 13

Page 14

tYPE

Input type

uOLt

Voltage

rtd

RTD

tc

Thermocouple

CUrEnt

Current

rAnge

Range

10

± 10 V

1

± 1 V

5

± 5 V

1.5

(±1 to 5) V

4-2

20

(4 to 20) mA

20

(0 to 20) mA

10

(0 to 10) mA

0.1

± 100 mV

Displayed if 

VOLTAGE 

input is selected

Displayed if 

CURRENT

input is selected

Lin

Linearisation type

nOnE

None Linear

S9rOOt

Square root

rOOt32

Power 3/2

rOOt52

Power 5/2

USEr

User defined

Pt100

Pt100 European

Ni  120

Ni120

CA

K

Current/Voltage

JISC

Pt100 USA/Japanese

USEr

User defined

RTD

J

J

t

T

r

R

S

S

E

E

L

L

n

N

b

B

USEr

User defined

Thermocouple

SE9ntS

Segments

EntEr

Enter

Enter Value

Enter value

Enter value

etc. etc.

In  1

Electrical co-ordinate 1

OUt  1

PV co-ordinate 1

Stndrd

Standard manual scaling applies

Auto

Auto scaling applies

En9  LO

Engineering low

Enter value

En9  HI

Engineering high

Enter value

APPLy

Apply auto scale

Enter value

Enter value

Enter value

Enter value

bUrn

Burnout

H i

High 

FILtEr

Filter

Enter value

APL  Lo

Apply electrical input low

HI  UAL

ScALE

Scaling method

Lo  UAL

l o

Low 

USEr  L

User linearisation

InPUt

units

Temperature unit

deg      c

Degrees C

deg      f

Degrees F

88888.8

1 DP

...Etc...

8.88888

5 DP

APL  HI

Apply electrical input high

dec      pl

Decimal places

Содержание DM3600U

Страница 1: ...RESETTING THE DEVICE 13 12 0 INPUT MENU STRUCTURE 14 17 13 0 OUTPUT MENU STRUCTURE 18 20 14 0 SYSTEM MENU STRUCTURE 21 22 15 0 FAULT FINDING 23 Status Instruments Ltd Status Business Park Tewkesbury Glos GL20 8FD Tel 44 0 1684 296818 Fax 44 0 1684 293746 Email sales status co uk Web www status co uk 52 314 2367 02 Issue Web 4 DM3600U INDEX Single Channel Universal Input 6 Digit Indicator Important...

Страница 2: ...ion to an installation over voltage Category II supply pollution degree 2 The supply voltage and frequency must remain within the limits stated on the product label The mains supply to the unit must be protected by an external 1 A fuse and a suitable switch or circuit breaker must be located close to the equipment in order to isolate the supply SIGNAL INPUT OUTPUTS All signal input and communicati...

Страница 3: ...rt conductor tail sufficiently into 2 then release screwdriver Ensure no loose wire strands protrude Page 4 Power must be removed from unit before adding removing a pod Slot 1 alarm 1A and 1B should be positioned on the left side of the unit looking from the front to correspond to front panel alarm indicator Slot 2 alarm 2A and 2B is positioned on the right To install an Option Pod slide back the ...

Страница 4: ...lease contact your supplier When fitted this option provides the user with either 4 or 2 wire RS485 serial communications together two digital inputs Connections are made via a RJ45 connector A 0 5 m interface is supplied with this Page 5 Page 6 Material ABS PC Flammability IEC707 FV0 UL 94VO Weight 230 g Panel cut out 92 x 45 mm 1 2 3 4 5 R Load 1 2 3 4 5 V R Load Max RLoad 1 K 4 3 ISOLATED 4 TO ...

Страница 5: ...tom 999 to 9999 Accuracy Linearisation Cold Junction Error Cold Junction Tracking Cold Junction Range 0 04 FS 0 04 reading or 0 5 C whichever is greater BS 4937 IEC 584 3 Custom 0 5 C 0 05 C C 20 to 60 C Thermal Drift Zero 4 uV C Span 0 02 C VOLTAGE INPUT Basic Accuracy 0 04 FS 0 04 of reading Thermal Drift 0 01 C Input Impedance 1 MΩ Linearity Linear X X 3 2 X 5 2 Custom Range 100 mV 1 V 5 V 10 V...

Страница 6: ...ODBUS RTU protocol and can be used with Status own M Config software Physical Layer 4 wire or 2 wire half duplex RS485 Protocol MODBUS RTU format Breakdown Isolation 500 VAC Maximum Fan out 32 units can be increased with repeaters Termination Standard RS485 The DM3600 is configured using the three keys on the front panel The unit has two modes of operation The first is Run mode This will automatic...

Страница 7: ...If enabled this gives access to the relevant alarm setpoints To revert to Run mode press these keys up to 4 times Show electrical value e g 4 to 20 mA input Shows secondary value i e total or rate If enabled this will clear total and or latched alarms Perform clear function Show upper 6 digits of Total RUN MODE RATE OR TOTAL DISPLAYED Edit setpoints menu shortcut Followed by Enter menu mode 8 2 RU...

Страница 8: ...nge 10 10 V 1 1 V 5 5 V 1 5 1 to 5 V 4 2 20 4 to 20 mA 20 0 to 20 mA 10 0 to 10 mA 0 1 100 mV Displayed if VOLTAGE input is selected Displayed if CURRENT input is selected Lin Linearisation type nOnE None Linear S9rOOt Square root rOOt32 Power 3 2 rOOt52 Power 5 2 USEr User defined Pt100 Pt100 European Ni 120 Ni120 CA K Current Voltage JISC Pt100 USA Japanese USEr User defined RTD J J t T r R S S ...

Страница 9: ...the input to the relevant input_lo and input_hi values see table overleaf for input_lo hi values The PV_lo PV_hi values shown overleaf equate to the En9LO and En9Hi entries Scaling is subsequently applied according to the graph overleaf The straight line illustrated overleaf will change if a non linear linearity type is selected If the user requires strict control over out of range limits user lin...

Страница 10: ...RTD input type is chosen 13 0 OUTPUT MENU STRUCTURE Page 17 Page 18 DELAyA Alarm delay dEUA Deviation Enter value Enter value Enter value in seconds Enter value HI High dEUIAt Deviation tESt Test dISAbL Disable nonInU Non inverting InUErt Inverting RELAY OUTPUT MENU OUt 1 Output 1 OUt 2 Output 2 off Off lo Low enable Enable SEtPA Setpoint RE TRANSMISSION mA OUTPUT MENU rEtrAn mA Output scaled to r...

Страница 11: ...OINT A The setpoint value defines the engineering value associated with an alarm For example if an alarm is required when the flow exceeds 10 000 kg h the setpoint will be set to 10 000 ALARM ACTION This defines the behaviour of the alarm when the setpoint is reached HYSTERISIS The hysterisis value is the difference between the points at which the alarm triggers and releases expressed in the relev...

Страница 12: ...MENU ACCESS PASSCODE When accessing the menus from Run mode the user is prompted for this passcode If it is zero default then there is no prompt and the password function is disabled If the password is forgotten please contact your supplier USER OFFSET This value is used to offset the scaled process variable by a fixed amount MENU TIME OUT This sets the amount of time after which the display will ...

Страница 13: ...HOWS DISPLAY SHOWS DP Err IS DISPLAYED OP CAL IS DISPLAYED IP CAL IS DISPLAYED POSSIBLE CAUSE No power Input is out of range above maximum Input is out of range below minimum The displayed value excluding total is greater than 6 digits i e 999999 The output pod has been corrupted The input calibrated data has been corrupted ACTION Check power supply connections Check that the engineering high valu...

Отзывы: