Maintenance may only by carried out by a service and maintenance engineer.
8.4
Fault table 'insufficient hot water'
If the appliance is not supplying enough hot water, this can have a variety of causes.
If this is the case, consult
’Table 8.3 Insufficient hot water’
Table 8.3 Insufficient hot water
Characteristic
Cause
Measure
Observation
Insufficient hot water
Set water temperature
(T
set
) too low
Set the control thermostat to a higher position. See paragraph
Hot water supply used
up.
1. Reduce the amount of hot water that you use. Give the
appliance enough time to heat up the water.
2. If this fault occurs regularly, then check whether the maximum
thermostat is switching. If this is the case, then check that the
circulation- and/or shunt pump are working properly.
If the fault has not been rectified and nor can a cause be
determined, then disconnect the appliance from the mains, shut off
the gas valve and warn your installer.
Содержание SCE 65-400
Страница 2: ...your installer ...
Страница 4: ...4 SCE Instruction Manual ...
Страница 8: ...8 Instruction Manual SCE gis ...
Страница 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Страница 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Страница 20: ...Installation 20 Instruction Manual SCE 3 is Figure 3 1 Top and front of the appliance IMD 0145 ...
Страница 42: ...Installation 42 Instruction Manual SCE 3 is ...
Страница 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Страница 64: ...Maintenance 64 Instruction Manual SCE 9 s ...
Страница 67: ...Release R 1 0 Uk 67 A Appendices A 1 Introduction This appendix contains The Electrical diagram SCE is ...
Страница 70: ...Appendices 70 Instruction Manual SCE A is ...