Installation
40
Instruction Manual SCE
3
is
To check the supply pressure and burner pressure, proceed as follows:
1. Disconnect the appliance from the mains. See paragraph
’7.3.2 Disconnecting the appliance from the mains’
2. There are two test nipples on the gas control (
). The test nipple
f
is used for checking the supply pressure. The other test nipple on the gas
control is not used. The manifold test nipple
h
is used for measuring the
burner pressure.
Sealing screws are located inside the test nipples. Undo both sealing screws
by a few turns. Do no completely undo them; otherwise it is awkward
retightening them.
3. There are two test nipples on the gas control
h
.
4. Open the gas supply and vent the gas pipe supply via test nipple
f
.
5. Connect a manometer to the top test nipple
f
as soon as gas starts to come
out of this nipple.
6. Switch on the voltage to the appliance using the main switch on the appliance.
7. Switch the control thermostat to its highest setting and put the appliance into
operation by switching the O/I switch to
position I
.
8. The warm-up cycle starts and the burner
tray
will ignite after a short time.
9. After the burner bed has ignited, you have to wait for approximately 1 minute
before you can read the dynamic pressures.
10. Use the manometer to read the supply pressure at the test nipple
f
View
n
Remark
Consult the manager of the gas mains supply if the supply pressure is not
correct.
11. Use the manometer to read the burner pressure at the manifold test
nipple
h
. View
Table 3.9
Conversion data for appliance category II
2H3+
DESCRIPTION
Unit
SCE
80-115
SCE
80-140
SCE
80-180
SCE
95-199
SCE
95-260
SCE
70-360
SCE
65-400
SCE
65-500
Data natural gas, gas category 2H
Diameter of injectors
mm
2.90
3.20
3.20
3.30
2.95
3.20
3.30
3.90
G20
Supply pressure
mbar
20
20
20
20
20
20
20
20
Burner pressure
mbar
8.5
8.6
7.8
8.5
8.5
9.2
7.8
11.5
Data on LP gas, gas category 3+
Diameter of injectors
mm
1.60
1.70
1.60
1.75
1.50
1.70
1.75
2.25
G30 (butane)
Supply pressure
mbar
30
30
30
30
30
30
30
30
Burner pressure
(1)
mbar
-
-
-
-
-
-
-
-
G31 (propane)
Supply pressure
mbar
37
37
37
37
37
37
37
37
Burner pressure
(1)
mbar
-
-
-
-
-
-
-
-
1.
If using a flat sealing plate or high-low control program, the burner pressure is adjusted so that it is the same as the supply pressure.
In practice however the burner pressure will be lower.
Содержание SCE 65-400
Страница 2: ...your installer ...
Страница 4: ...4 SCE Instruction Manual ...
Страница 8: ...8 Instruction Manual SCE gis ...
Страница 12: ...Introduction 12 Instruction Manual SCE 1 gis ...
Страница 18: ...Operating the appliance 18 Instruction Manual SCE 2 gis ...
Страница 20: ...Installation 20 Instruction Manual SCE 3 is Figure 3 1 Top and front of the appliance IMD 0145 ...
Страница 42: ...Installation 42 Instruction Manual SCE 3 is ...
Страница 46: ...Filling and draining 46 Instruction Manual SCE 4 gis ...
Страница 64: ...Maintenance 64 Instruction Manual SCE 9 s ...
Страница 67: ...Release R 1 0 Uk 67 A Appendices A 1 Introduction This appendix contains The Electrical diagram SCE is ...
Страница 70: ...Appendices 70 Instruction Manual SCE A is ...