Locate the hot water (outlet) & cold water (inlet) pipes 

4. 

to the water heater.
Locate the slit running the length of a section of pipe 

5. 

insulation.
Spread the slit open and slip the insulation over the 

6. 

cold water (inlet) pipe. Apply gentle pressure along the 

length of the insulation to ensure that it is fully seated 

around the pipe. Also, ensure that the base of the 

insulation is 

fl

 ush with the water heater. Once seated, 

secure the insulation with duct tape, electrical tape, or 

equivalent.
Repeat steps 5 and 6 for the hot water (outlet) pipe.

7. 

Add additional sections of pipe insulation as needed.

8. 

Figure 6  
T&P Relief Valve Insulation 

T&P Relief Valve

T&P Relief Valve 

Drain Line

Manual Relief Lever

T&P Relief Valve Insulation

Electrical Requirements

If you lack the necessary skills required to properly install the 

electrical wiring to this water heater, do not proceed but have a 

quali

fi

 ed electrician perform the installation.

When making the electrical connections, always make sure:

The electrical service provides 240 VAC to the water heater 

• 

for proper operation. DO NOT use 208 VAC.

Wire sizes and connections comply with all applicable 

• 

codes or in the absence of local or state codes follow 

NFPA-70, the National Electrical Code-current edition.

Wiring enclosed in approved conduit (if required by local 

• 

codes).

The water heater and electrical supply are properly  

• 

grounded.

The electrical supply has the proper overload fuse or 

• 

breaker protection.

Figures 8A & 9 are provided as reference drawings. Always 

reference the wiring diagram located on the water heater for the 

correct electrical connections and 

connect the electrical supply 

to the water heater in accordance with local utility requirements 

and codes.

When installing the electrical wiring to the water heater:

Although this water heater is equipped with “Dry Fire” 

1. 

protection circuitry, be sure tank is completely filled with 

water, and all air is purged from the tank before making 

any electrical connections. See “Draining and Flushing 

Section”.
Turn off power to the electrical wiring for the water heater at 

2. 

the circuit breaker/fuse box.
Remove the left louvered access panel (when facing the 

3. 

water heater) by loosening the screws securing it to the 

water heater.
Loosen the screws securing the electrical junction box 

4. 

cover to the water heater and set aside. 
Connect the electrical supply to the water heater.  

5. 

A standard 1/2 inch opening has been made in the junction 

box for conduit connections. 

Connect ground wire to green ground wire in the electrical 

6. 

junction box of the water heater.  
Reinstall the junction box cover.

7. 

Reattach the left louvered access panel to the water heater 

8. 

and secure it using the screws loosened earlier.
Turn on electrical power to the water heater.

9. 

Press the power button to turn the water heater on, then 

10. 

press the Efficiency button to set the operating mode. 

NOTE:

 The water heater will conduct a system diagnostic  

(approximately 8 minutes) prior to returning to operation.
Once the diagnostic sequence has finished, the fan should 

11. 

turn on.  

NOTE:

 The heat pump’s fan will not turn on if the incoming 

water temperature is less than 59 °F and/or the ambient 

air temperature is above 109 °F or below 45 °F. Should the 

internal diagnostics detect a problem with the heat pump, 

an error message will be displayed. 
Set the operational mode. For standard installation, the 

12. 

Hybrid Mode offers the best combination of efficiency 

and hot water delivery. For detailed descriptions of all 

operational modes see “Adjusting the User Interface 

Module/Operational Modes” section.

WARNING

Electric Shock Hazard

Disconnect power before 
servicing.

Replace all parts and panels 
before operating.

Failure to do so can result in 
death or electrical shock.

 

 

 

 

WARNING

Fire Hazard

Use 10 gauge solid copper 
wire.

Use a UL listed or 
CSA approved strain relief. 

Connect ground wire to green 
ground wire.

Failure to do so can result in 
death, fire, or electrical shock.

Figure 7
Louvered Panel

Содержание 318258-000

Страница 1: ...Information 3 Consumer Responsibilities 3 Unpacking Instructions 3 4 Location Requirements 4 Water System Piping 5 6 Temperature Pressure Relief Valve 7 8 Electrical Requirements 8 9 Installation Checklist 10 Operating Your Water Heater 11 13 Before Using 11 Water Temperature Regulation 11 Adjusting the User Interface Module Operational Mode 12 Operational Conditions 13 Maintenance of Your Water H...

Страница 2: ...s extremely flammable To reduce the risk of injury under these conditions it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system When hydrogen is present there will probably be an unusual sound such as air escaping through the pipe as the water begins to flow There should be no smoking or...

Страница 3: ...eipt as proof of purchase Basic Operation Fundamentals The Heat Pump Water Heater HPWH is an integrated heat pump water heater unit having an 850 watt compressor and external coil heat exchanger with backup electric elements See Figure 1 When in Efficiency Mode the heat pump draws heat from the ambient air in the room and transfers it to the water in the tank through the coil heat exchanger While ...

Страница 4: ...read all instructions before attempting to assemble and install this product After installation dispose of recycle all packaging materials Location Requirements Site location Select a location near the center of the water piping system The unit must be installed indoors and in a vertical position on a level surface The flooring beneath the water heater must be able to support the weight of the wat...

Страница 5: ...hown in Figure 4 If installing the water heater in a closed water system 5 install an expansion tank in the cold water line as specified under Closed System Thermal Expansion Install a shut off valve in the cold water inlet line It 6 should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater Install a discharge l...

Страница 6: ...des Use appropriate primer and glue to cement the condensate drain lines to the heat pump drain pan NOTE The heat pump drain pan is ABS and the two condensate drain pipes should be PVC If a condensate pump is installed it should shut off the heat pump in the event the condensate pump fails or the float switch in the pump activates See Condensate Pump Installation section Closed System Thermal Expa...

Страница 7: ...lve and the end of the discharge line Shall terminate a maximum of six inches above a floor drain or external to the building In cold climates it is recommended that the discharge pipe be terminated at an adequate drain inside the building Shall be of material listed for hot water distribution Shall be installed to allow complete drainage of both the valve and discharge line Temperature Pressure R...

Страница 8: ...lled with water and all air is purged from the tank before making any electrical connections See Draining and Flushing Section Turn off power to the electrical wiring for the water heater at 2 the circuit breaker fuse box Remove the left louvered access panel when facing the 3 water heater by loosening the screws securing it to the water heater Loosen the screws securing the electrical junction bo...

Страница 9: ...7 Press the power button to turn the water heater on 8 and select the desired operational mode After about 8 minutes the heat pump will turn on Test the operation of the shut off switch by unplugging 9 the condensate pump and filling the condensate reservoir with water until the float switch opens the circuit The heat pump should turn off and the error code 10 CONDENSATE DRAIN ALARM will appear on...

Страница 10: ... free of leaks Heater completely filled with water See Water Piping System section Closed system pressure buildup precautions installed See Closed System Thermal Expansion section Mixing valve when applicable installed per manufacturer s instructions See Water Temperature Regulation section INSTALLATION CHECKLIST Condensate Drain Line Installation Must be located with access to an adequate drain o...

Страница 11: ...hing in the red reset button located on the ECO block If the ECO continues to shut off the water heater contact a qualified person for service Water Temperature Regulation Water temperature over 125 F can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being scalded Feel water before bathing or showering Temperature limiting valves are availab...

Страница 12: ... the User Interface are touch sensitive and require only a light touch to actuate EFFICIENCY Efficiency Mode Is the most energy efficient mode This mode uses the heat pump to heat water in the tank The elements are not used unless the ambient operating temperature is below 45 F or above 109 F If hot water demands are not met in Efficiency Mode it may be necessary to switch to Hybrid Mode HYBRID Hy...

Страница 13: ...ard These noises are common and may result from the following Normal expansion and contraction of metal parts 1 during periods of heat up and cool down Sediment buildup on or around the elements could 2 create varying amounts of noise and may cause premature tank failure Drain and flush the tank as directed under the Draining and Flushing section The heat pump compressor or fan running 3 Stacking ...

Страница 14: ...PORTANT Do not turn on power to the water heater unless it is completely filled with water To ensure that the tank is full open a hot water faucet and allow the water to run until the air is purged and the water flows uninterrupted from the faucet Press the power button to turn the water heater on 8 NOTE The water heater will conduct a system diagnostic prior to operation If the water heater is go...

Страница 15: ...Air Filter Remove and inspect clean if needed and reinstall Condensate drain pan and condensate lines The lower metal drain pan for standing water which may indicate a clogged condensate drain pan condensate lines or plumbing leak Leaking or damaged water piping Presence of corrosive materials in the installation area Presence of combustible materials near the water heater After servicing this wat...

Страница 16: ... OPEN OR AD ERROR 1 Upper Temperature Sensor is not functioning Contact a qualified person to service the unit 1 LOWER TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Lower Temperature Sensor is not functioning Contact a qualified person to service the unit 1 DISCHARGE TEMP SENSOR SHORT OR OPEN OR AD ERROR 1 Discharge Temperature Sensor is not functioning Contact a qualified person to service the unit 1 C...

Страница 17: ...n is at the top Insulate exposed piping 5 Repair hot water leaks 6 Call qualified person for service 7 Drain and flush tank Water conditioning may 8 be necessary to minimize build up HIGH OPERATION COSTS Temperature set point too high 1 Air filter dirty 2 Electric mode selected 3 Water connections to unit reversed 4 Heat lost thru long run of exposed 5 pipe Hot water leak at faucet or piping 6 Sed...

Страница 18: ...14 Drain Valve 15 Protective Plastic Cover 16 ECO Cover 17 Control Board 18 Relay 19 EPS Cover 20 Ambient Coil Discharge Temperature Sensor 21 Upper Lower Tank Temperature Sensor 22 Run Capacitor 23 Control Board Module Fuses REPAIR PARTS Repair parts may be ordered through your plumber local distributor home improvement center or by calling 1 800 365 0024 When ordering repair parts always give th...

Страница 19: ...19 NOTES ...