b.  Actuation Wiring 

 

- The actuation circuit wiring is critical to the proper operation of the SDRP 
- Take care in making and securing all electrical connections 
- Water and corrosive atmospheres are never good for electrical circuits. Take care to 
prevent water and corrosive atmospheres from damaging electrical connections 
- Wire to-be UL listed Plenum cable, 18 awg, solid annealed bare copper per ASTM B3 
with PVC jacket (Carol E3602S.41.03 or equal). 
- Field wiring must be protected by metal conduit or equal. 
- Terminate as needed using Deutsch terminals and connectors as described in part no. 
830006.  Crimp terminals and crimp using #5 setting for 18 gauge pin. After crimping, 
use Kester 1544 soldering flux and solder using no clean, lead free SN100 solder to 
bond terminal to solid formed wire. 

 

9. Warranty 

 

LIMITED WARRANTY STATEMENT 

 
Fireaway Inc. represents that this product is free from defects in material and workmanship, and 
it will repair or replace any product or part thereof which proves to be defective in workmanship 
or material for a period of eighteen (18) months from the date of first shipment from our factory. 
Defective units should be returned shipment prepaid to the factory. 
 
Fireaway  Inc.  will  repair  or  replace  and  return  shipping  prepaid.  Return  or  repair  shall  be  the 
purchaser’s sole remedy for defect. 
 
Limitations of Liability 
 
This  warranty  does  not cover  equipment  damaged  during  shipment  or  by  misuse,  accident,  or 
negligence, or which has been repaired or altered by others. Fireaway Inc. shall not under any 
circumstances be liable for special or consequential damages such as, but not limited to, damage 
or loss of property or equipment, loss of profits or revenue, cost of capital, cost of purchased or 
replacement goods, or claims by customers of the original purchaser. Remedies set forth herein 
to the original purchaser and all others shall not exceed the price of the equipment supplied. 
 
This warranty is exclusively and expressly in lieu of all other warranties, whether expressed or 
implied, including warranty of merchantability or fitness. 
 
A

 DETAILED MANUAL MAY BE OBTAINED BY CONTACTING THE MANUFACTURER

 

 

 

5852 Baker Road 

Minnetonka, MN 55345 

U.S.A. 

 

Tel: 925-935-9745 

Fax: 952-935-9757 

www.statx.com 

Содержание SDRP

Страница 1: ...Stat X Dual Release Panel SDRP Installation Operation and Owner s Manual...

Страница 2: ...erview 3 Component Description a Control Panel b Cable Harness c Alarm Test Module d Detection Wiring e Actuation Wiring 4 System Design and Installation 5 Inspection and Maintenance 6 System Alarms a...

Страница 3: ...t aluminum enclosure surrounds the military qualified electronic components The SDRP provides electrical supervision of fire detection release manual activation as well as battery condition The SDRP i...

Страница 4: ...rom the elements it s always good practice to keep electronics away from water oil and other conductive materials Ensure the SDRP is not located in the hazard area and is protected in some manner agai...

Страница 5: ...ion and Operation Stat X generators must be securely mounted and aimed per the Hazard Analysis Field wiring from the SDRP to each generator may be wired in series or in parallel Only two generators ma...

Страница 6: ...igure 2 SDRP Controls and Indications Figure 3 SDRP Labeling The SDRP panel includes two detection zones and two releasing zones The SDRP can be ordered in one of two programming configurations Serial...

Страница 7: ...Input Switch will also actuate both actuation zones PN 830001 01 Dual Detection Zones and Dual Releasing Zones Each detection zone will actuate individual separate actuation zones A single dedicated...

Страница 8: ...s use color coded ty wraps along with labels which indicate the cable wire function Note It s important to note that while the Stat X generators are not polarized the Alarm Test Module PN 830002 which...

Страница 9: ...he ability to live test the SDRP panel and detection circuitry When a detection circuit closes in Alarm the Alarm Module senses the electrical load and simulates a system actuation A red LED in the Al...

Страница 10: ...roven MIL 26482 metal shell connector to link the manual switch to the SDRP panel manual release input circuit The normally open toggle switch used with the Manual Release Switch is protected by a lab...

Страница 11: ...n End of Line device completing a loop back to the SDRP If a Fire occurs the outer and inner insulating jackets of the linear thermal wire melt allowing the individual conductors of the linear thermal...

Страница 12: ...gh an end of line device completing a loop back to the SDRP If a fire occurs the normally open contacts in the spot thermal close This change in electrical resistance is interpreted by the SDRP as a f...

Страница 13: ...The end of line device EOL PN 830007 provides a series resistance of 470k ohms The EOL consists of a two position Deutsch connector with an over molded 470k ohm resistor The EOL provides a high resist...

Страница 14: ...he SDRP and each spot thermal detector must be at a minimum UL Listed Plenum wire 18 awg Parallel field wiring is used between detectors Detection field wiring must be protected in emt conduit between...

Страница 15: ...s easily supervised by the SDRP Parallel field wiring is acceptable but must be protected in emt conduit as individual Stat X generators are not supervised by the SDRP Wiring connections must be secur...

Страница 16: ...k Manual Release Switch for any damage or other changes Annual Inspection 1 Before performing any detection circuit tests attach alarm module PN 830002 to both SDRP actuation circuits 2 Flip the test...

Страница 17: ...ly use our PN 830009 as a replacement 1 See figures 10 11 below 2 Remove panel from mounting position 3 Remove pull pin and flip toggle switch to Disable System position 4 Replace pull pin 5 Disconnec...

Страница 18: ...Fireaway Inc Version 1 5852 Baker Road 10 2017 Minnetonka MN 55345 P N 19112 18 Figure 16 SDRP battery replacement data to be completed annually when batteries are replaced...

Страница 19: ...nt Panel Display System OK Green LED ON System Trouble Yellow LED OFF Indicates Status Detection Field Wiring Continuous circuit with correct resistance Actuation Field Wiring Continuous circuit with...

Страница 20: ...generator to field wiring connection is intact Check for corrosion at Stat X generator to field wiring connection Check actuation circuit for any breaks or damage Verify Stat X generator has not disc...

Страница 21: ...F Type XCR 830025 xxx Linear Thermal Wire 135o F Type XLT 8 Miscellaneous Notes a Battery Storage STORAGE Store in a cool regulated preferably below 21 C and in any case below 30 C dry and ventilated...

Страница 22: ...t thereof which proves to be defective in workmanship or material for a period of eighteen 18 months from the date of first shipment from our factory Defective units should be returned shipment prepai...

Отзывы: