Stat-X SDRP Скачать руководство пользователя страница 16

Fireaway Inc.

 

 

Version 1 

5852 Baker Road 

 

10/2017 

Minnetonka, MN 55345 

 

P/N 19112 

 

16 

4. Hazard Analysis 

 

Refer to the current Stat-X 

owner’s manual PN19001 for generator installation requirements. 

 
5. Inspection and Maintenance 

 

The SDRP panel is designed to be simple and reliable.  Inspection and maintenance consists of 
the following: 
 
Daily Inspection if possible 

With the SDRP panel in 

“Armed” mode, flip the test toggle switch up or down. 

- The 

“System OK” LED should appear 

green

 

… 

 
- If the 

“System OK” LED does NOT appear 

green

 and the 

yellow

 

“System Trouble” 

LED appears Yellow                      Go to system trouble shooting 

… 

 
- If NO 

LED’s are ON                     Go to system trouble shooting … 

 

Monthly Inspection 

Visually inspect field wiring 

… 

- Check Automatic Detection circuit for any damage or other changes. 
- Verify spot thermal detectors or linear thermal wire has not been painted, damaged or 
blocked from thermal sensing 
- Check Stat-X actuation wiring for any damage, contact corrosion or changes which 
might affect proper operation. 
- Check detection circuit end of line device for any damage or other changes. 
- Check Manual Release Switch for any damage or other changes. 

 

Annual Inspection 

1.  Before performing any detection circuit tests, attach alarm module PN 830002 to both 

SDRP actuation circuits. 

2. 

Flip the “test” toggle switch on the SDRP to verify “System OK” operation. 

3.  Spot thermal detection test 

a.  Use a heat gun to heat each spot thermal sensor to its alarm set point.  Use a 

thermocouple to verify proper temperature. 

b.  Each alarm module will latch in a 

“fire” condition when the spot thermal sensor 

reaches its alarm set point. 

c.  Allow each spot thermal sensor to cool below its alarm set point. 
d.  Press the 

“System Reset” button on the alarm module to clear the “alarm” 

condition. 

e.  Continue testing the remaining spot thermal sensors. 

4.  Linear thermal detection test 

a.  Linear thermal detection wiring cannot be tested using a heat gun!! 
b.  Remove the PN 830007 end of line device from the detection circuit. 
c.  Replace the end of line with a PN 830003 manual test switch. 
d.  Flip the Manual Test Switch toggle to simulate a linear thermal 

“alarm” condition. 

e.  Eac

h alarm module will latch in a “fire” condition when the Manual Test Switch is 

activated. Return the manual test switch to normal operation. 

f.  Press the 

“System Reset” button on each alarm module to clear the “Alarm” 

condition. 

Содержание SDRP

Страница 1: ...Stat X Dual Release Panel SDRP Installation Operation and Owner s Manual...

Страница 2: ...erview 3 Component Description a Control Panel b Cable Harness c Alarm Test Module d Detection Wiring e Actuation Wiring 4 System Design and Installation 5 Inspection and Maintenance 6 System Alarms a...

Страница 3: ...t aluminum enclosure surrounds the military qualified electronic components The SDRP provides electrical supervision of fire detection release manual activation as well as battery condition The SDRP i...

Страница 4: ...rom the elements it s always good practice to keep electronics away from water oil and other conductive materials Ensure the SDRP is not located in the hazard area and is protected in some manner agai...

Страница 5: ...ion and Operation Stat X generators must be securely mounted and aimed per the Hazard Analysis Field wiring from the SDRP to each generator may be wired in series or in parallel Only two generators ma...

Страница 6: ...igure 2 SDRP Controls and Indications Figure 3 SDRP Labeling The SDRP panel includes two detection zones and two releasing zones The SDRP can be ordered in one of two programming configurations Serial...

Страница 7: ...Input Switch will also actuate both actuation zones PN 830001 01 Dual Detection Zones and Dual Releasing Zones Each detection zone will actuate individual separate actuation zones A single dedicated...

Страница 8: ...s use color coded ty wraps along with labels which indicate the cable wire function Note It s important to note that while the Stat X generators are not polarized the Alarm Test Module PN 830002 which...

Страница 9: ...he ability to live test the SDRP panel and detection circuitry When a detection circuit closes in Alarm the Alarm Module senses the electrical load and simulates a system actuation A red LED in the Al...

Страница 10: ...roven MIL 26482 metal shell connector to link the manual switch to the SDRP panel manual release input circuit The normally open toggle switch used with the Manual Release Switch is protected by a lab...

Страница 11: ...n End of Line device completing a loop back to the SDRP If a Fire occurs the outer and inner insulating jackets of the linear thermal wire melt allowing the individual conductors of the linear thermal...

Страница 12: ...gh an end of line device completing a loop back to the SDRP If a fire occurs the normally open contacts in the spot thermal close This change in electrical resistance is interpreted by the SDRP as a f...

Страница 13: ...The end of line device EOL PN 830007 provides a series resistance of 470k ohms The EOL consists of a two position Deutsch connector with an over molded 470k ohm resistor The EOL provides a high resist...

Страница 14: ...he SDRP and each spot thermal detector must be at a minimum UL Listed Plenum wire 18 awg Parallel field wiring is used between detectors Detection field wiring must be protected in emt conduit between...

Страница 15: ...s easily supervised by the SDRP Parallel field wiring is acceptable but must be protected in emt conduit as individual Stat X generators are not supervised by the SDRP Wiring connections must be secur...

Страница 16: ...k Manual Release Switch for any damage or other changes Annual Inspection 1 Before performing any detection circuit tests attach alarm module PN 830002 to both SDRP actuation circuits 2 Flip the test...

Страница 17: ...ly use our PN 830009 as a replacement 1 See figures 10 11 below 2 Remove panel from mounting position 3 Remove pull pin and flip toggle switch to Disable System position 4 Replace pull pin 5 Disconnec...

Страница 18: ...Fireaway Inc Version 1 5852 Baker Road 10 2017 Minnetonka MN 55345 P N 19112 18 Figure 16 SDRP battery replacement data to be completed annually when batteries are replaced...

Страница 19: ...nt Panel Display System OK Green LED ON System Trouble Yellow LED OFF Indicates Status Detection Field Wiring Continuous circuit with correct resistance Actuation Field Wiring Continuous circuit with...

Страница 20: ...generator to field wiring connection is intact Check for corrosion at Stat X generator to field wiring connection Check actuation circuit for any breaks or damage Verify Stat X generator has not disc...

Страница 21: ...F Type XCR 830025 xxx Linear Thermal Wire 135o F Type XLT 8 Miscellaneous Notes a Battery Storage STORAGE Store in a cool regulated preferably below 21 C and in any case below 30 C dry and ventilated...

Страница 22: ...t thereof which proves to be defective in workmanship or material for a period of eighteen 18 months from the date of first shipment from our factory Defective units should be returned shipment prepai...

Отзывы: