Fireaway Inc.
Version 1
5852 Baker Road
10/2017
Minnetonka, MN 55345
P/N 19112
20
Front Panel Display
System OK
– Green OFF
System Trouble
– Yellow ON
Indicates
Status
Detection Field Wiring Problem
Possible Open Condition
•
Check to see if SDRP to field wiring circular
connector is tight and connected
•
Check to see if end of line device is in place
•
Check all sensors and wiring
•
Check for any wiring damage or breaks
Actuation Field Wiring Problem
Possible Open Condition
•
Check to see if SDRP to field wiring circular
connector is tight and connected
•
Check Stat-X generator to field wiring connection
is intact
•
Check for corrosion at Stat-X generator to field
wiring connection
•
Check actuation circuit for any breaks or damage
•
Verify Stat-X generator has not discharged
Manual Release Switch Problem
Possible Open Condition
•
Check to see if SDRP to field wiring circular
connector is tight and connected
•
Check field wiring to Manual Release Switch
circular connector is tight and connected
•
Check field wiring to manual release switch for any
breaks or damage
Disable Switch Position
Disable Switch Position
•
Check the
“Arm System-Disable System” toggle
switch is in the proper position
Internal Battery Problem
Possible Low Voltage Condition
•
Check replacement date for batteries, if more than
three (3) years, replace batteries