washed clean. Consult Stat-X Safety Data Sheet for safety 

information.
6.

 Important! Any residue which is not cleaned up shortly 

following discharge can absorb moisture in air.

 A change in 

room temperature during a fire event or discharge can affect 

humidity and it is important to reduce the enclosure humidity 

as soon as possible following discharge.
7.  Remove spent generators, being sure to wear gloves or 

other hand protection. The generators will remain quite warm 

to the touch for a time after actuation.
8.  Dispose of spent generators per applicable federal, state, 

and local regulations
9.  Contact your Stat-X distributor immediately for replacement 

generators. Replacement and commissioning should only be 

undertaken by trained personnel

NOTE

WARNING

Before performing post fire maintenance procedures refer 

to the Stat-X Safety Data Sheet.

MAINTENANCE

General:

 To ensure proper operation of your fire suppression 

system, a systematic maintenance program is required.  

A periodic maintenance schedule must be instituted including 

an inspection log maintained for reference. The log should, 

at a minimum, record: (1) inspection interval, (2) inspection 

procedure performed, (3) maintenance performed, if any, 

because of inspection, and (4) the name of the responsible 

person performing the operation.

Preventive Maintenance. 

Fireaway suggests that a preventive 

maintenance program require, at a minimum, the following 

schedule:

Inspection Procedures

Weekly

1.  Check all electrical connections to ensure operation of the 

Stat-X generators in the event of a fire. If connected to a fire 

alarm control panel, check the panel status.
2.  Make a general visual inspection of all aerosol generators 

for damaged or missing parts, and visually inspect that 

generator mounting is secure.

Every Six Months

1.  Ensure access to hazard areas, lines of egress, and 

manual release stations are unobstructed and that there are 

no obstacles inhibiting the proper operation of the aerosol 

generators or distribution of the aerosol in the event of a fire.
2.  Inspect Stat-X aerosol generators for physical damage, 

such as cracks, dents, distortion, or corrosion. If damage 

is found, replace generator as instructed in the installation 

section of this manual.
3.  Inspect mounting brackets, clamps, and associated 

hardware for loose, damaged, or broken parts. Replace 

damaged parts and tighten all loose hardware.
4.  Inspect all manual release stations for damage, dirt, or 

distortion. Inspect station for signs of physical damage, replace 

if necessary.
5.  Inspect all electrical connections and run electrical 

continuity tests using an ohmmeter. Repair and replace as 

necessary.
6.  Replacement: The aerosol generators have an installed 

service life of fifteen (15) years. Generators are to be replaced 

fifteen years from the date code in the lower right corner of  

the product label as follows, the 2-digit numeric represents the 

year and then the month of shipment from the factory:

 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12

21 = 2021, 22 = 2022, etc. A unit marked 21 12, for  

example, would have shipped in December of 2021.

RECYCLING OF AEROSOL GENERATORS AFTER 

DISCHARGE:

In most cases the discharged generator can be disposed of 

in any landfill that handles industrial waste. However, local 

regulations must be researched and observed. 
Each discharged aerosol generator will contain the following 

material:
1.  Stainless steel outer shell – all
2.  Mild steel cross members (30E, 60E, 100E, 250E, 500E)
3.  Mild steel spacer ring - all
4.  Stainless steel inner shell, top and bottom plates, screens 

(all sizes), and cross members (1000E, 1500E, 2500E)
5.  Activated Alumina: CAS 1333-84-2 (Aluminum Oxide non-

fibrous) 

 30E  60E  100E  250E  500E  1000E 1500E 2500E

 20g  40g  100g  550g  970g  1670g 2350g 3600g

1.  Fiberglass rope (ø1cm x 50cm). 
2.  Ceramic Paper < 150g.
3.  Wire – 24gauge, PVC coated (< 1g)
4.  Trace chemicals: K2CO3 (water-soluble particulate 

“trapped” in unit during discharge).
Un-discharged generators taken out of service should be 

returned to your local authorized distributor for replacement 

and re-cycling.

LIMITED WARRANTY STATEMENT

Fireaway represents this product is free from defects in mate-

rial and workmanship, and it will repair or replace any product 

or part thereof which proves to be defective in workmanship 

or material for a period of eighteen (18) months from the date 

of first shipment from our factory. Defective units should be 

returned shipment prepaid to the factory.
Fireaway Inc. will repair or replace and return shipping 

prepaid. Return or repair shall be the purchaser’s sole remedy 

for defect.

Type of Survey: Weekly/Six Month/On 15th year 

Date:

Inspection Steps 

Yes 

No  N.A.

Perform a general visual inspection of all aerosol generators for damaged or missing parts. Examine each 

device for a puncture in the aluminum foil seal at orifice plate. Replace generator if foil is punctured or ripped.
Verify at the control panel for any fault or trouble indication with regards to the panel output releasing circuit(s). 

If there is an indicated releasing circuit fault, verify electrical signal connection from panel to each aerosol 

generator electrical initiator. Test using a multi-meter, the line resistance of the releasing circuit signal line. 

Replace aerosol generator if each electrical initiator resistance exceeds operational range of 1.4

Ω

 to 2.0

Ω

.

Inspect aerosol generators for physical damage that is not superficial, such as cracks, dents, distortion, or 

corrosion. If damage is found, replace generator as instructed in the owner’s manual.
Verify mounting brackets and straps, tightness of mounting hardware, and generator alignment are properly 

secured. Tighten all loose hardware or replace damaged parts.
Ensure paths of emergency egress from protected area is not impeded by an aerosol discharge as well as 

unobstructed access to manual pull stations and abort devices (where installed). Ensure there are no obstacles 

inhibiting the proper operation of the aerosol generators or distribution of aerosol in the event of fire.
Ensure automatic dampers (where fitted) are functional. Verify leakage areas identified during the original 

system design have not been modified.
Follow specific recommended manufacturer maintenance and test procedure for the fire detection/control 

system and fire detection devices, and per local codes.
The aerosol generators have an installed service life of fifteen (15) years. Replace each generator fifteen (15) 

years from the marked date code in the lower right corner of the product label.