Stat-X 30E Скачать руководство пользователя страница 3

Owner’s Manual

4

5

Operating/Temperature Range:

 Stat-X aerosol generators 

are listed to operate within a temperature range of -40°C to 

+54°C/-40ºF to 129.2ºF. Generators are sealed with a non-

permeable membrane and are unaffected by fluctuations in 

humidity and temperature.

EQUIPMENT INSTALLATION 

General.

 All Stat-X generators must be installed to facilitate proper 

operation, inspection, testing, and any other maintenance as may 

be necessary. Equipment must not be subject to mechanical, 

chemical, or other damage, which could render the unit inoperative. 

Equipment must be installed in accordance with all applicable 

standards and the contents of this section of the manual. 

WARNING

AEROSOL GENERATORS CONTAIN A FLAMMABLE SOLID 

AND MUST ONLY BE HANDLED, INSTALLED, AND SERVICED 

BY A TRAINED TECHNICIAN USING THE INSTRUCTIONS 

CONTAINED IN THIS SECTION. FAILURE TO FOLLOW THESE 

INSTRUCTIONS COULD CAUSE A PREMATURE DISCHARGE 

AND/OR POTENTIAL INJURY. 
Aerosol Generator Installation.

 The Stat-X aerosol generators 

should normally be located within the protected hazard area. 

The following installation instructions must be followed in 

the exact sequence outlined below to prevent accidental 

discharge, bodily injury, or property damage. 

WARNING

TO PREVENT PERSONAL INJURY, DE-ENERGIZE ALL 

ELECTRICAL CONNECTIONS PRIOR TO GENERATOR 

INSTALLATION.

Single Generator System:

1.  Position mounting bracket and securely fasten to wall, 

ceiling, or other supporting structure in a location and 

manner, which ensures the generator will not be subjected to 

accidental damage or movement.
2.  Remove generator from shipping container and inspect 

integrity of the non-permeable membrane and generator. Do 

not install if the membrane is ruptured in any way or if the 

housing has been damaged in shipment. Verify igniter integrity 

with Ohmmeter. Do not install if reading > 2 ohms.
3.  Securely attach generator to the mounting bracket with 

generator clamp taking care to ensure the clamp is free of the 

initiator mechanism and that all bolts are securely tightened.
4.  Position generator, via the bracket-mounting swivel, to 

allow for an unimpeded discharge upon activation. Care must 

be taken so that the generator does not directly discharge 

at close range at the wall, ceiling, or vertical surfaces of the 

equipment within the hazard area. 
5.  Taking care to ensure that power is off, connect electrical 

lines to the initiator fitting at the top of the generator. 

NOTE
THE INTERFACE BETWEEN THE GENERATOR AND THE 

FIRE ALARM CONTROL PANEL MAY REQUIRE ADDITIONAL 

ELECTRICAL DEVICES TO MEET LISTING COMPATIBILITY 

REQUIREMENTS. CONSULT FIRE ALARM CONTROL PANEL 

MANUAL FOR ANY LISTED SPECIAL FIELD DEVICES THAT 

MAY BE REQUIRED AS PART OF THE RELEASING CIRCUIT 

(E.G. EMATCH PROTECTION DEVICE, P/N 3005014).
WARNING
DE-ENERGIZE ALL ELECTRICAL CONNECTIONS PRIOR TO 

GENERATOR INSTALLATION. BE CAREFUL TO ENSURE THAT 

NO BODY PART IS PLACED DIRECTLY IN FRONT OF THE 

GENERATOR’S EXIT PORTS DURING INSTALLATION.

Multiple Generator System:

1.  Position mounting brackets and securely fasten to wall, 

ceiling, or other supporting structure in a location and 

manner, which ensures the generators will not be subjected to 

accidental damage or movement.
2.  Make sure mounting brackets are located in a manner to 

ensure a circular flow pattern and maximum dispersal and 

mixing of aerosol and air during discharge.
3.  Remove generator from shipping container and inspect 

integrity of the non-permeable membrane and generator. Do 

not install if the membrane is ruptured or punctured in any 

way or if the housing has been damaged in shipment. Verify 

igniter integrity with ohmmeter. Do not install if reading is 

outside a range of 1.4 – 2.0 ohms.

INSTALLATION

Facility Considerations 

Significant Obstructions/Agent Distribution: 

In cases where 

there is a large ratio of fixed equipment to total volume, or 

where the protected equipment is located in such a way as 

to present a barrier to the free flow and distribution of aerosol 

throughout the hazard area, the use of a larger number of 

smaller aerosol generators may be more suitable. This will allow 

for strategic placement of the aerosol generators and improved 

distribution characteristics throughout the protected area. 

Mounting:

 Stat-X aerosol generators are listed for both 

sidewall and ceiling locations and may be mounted on  

walls, beams, constructions, and columns, as long as the unit 

is securely bolted to the support structure and is mounted in a 

position where its “C-zone” (clearance zone where momentary 

peak temperature of the discharge will not exceed 75°C) will 

not impact on personnel, facilities, equipment or combustible 

materials located within the protected area. Housing clearance 

is required spacing of generator from combustibles and 

structural materials.

Aerosol Stream Characteristics

 

 

 Housing 

 

Model   C - Zone 

Height Max. 

Clearance

30E 

0.25m/9.8" 

0.5 to 1.22 m/19.7-48.0"  7mm/0.25"

60E 

0.35m/13.8" 

0.5 to 2.00 m/19.7-78.7"  7mm/0.25"

60ME  0.30m/11.8" 

0.5 to 2.00m/19.7-78.7"  7mm/0.25"

100E 

0.46m/18.1" 

0.5 to 2.50 m/19.7-98.4"  13mm/0.50"

250E 

0.75m/29.5"  0.5 to 2.75 m/19.7-108.3"  13mm/0.50"

500E 

1.27m/50.0"  0.5 to 3.50 m/19.7-137.8"  13mm/0.50"

1000E  2.30m/90.6"  0.5 to 4.88 m/19.7-192.1"  13mm/0.50"
1500E  2.00m/78.7"  0.5 to 4.88 m/19.7-192.1"  30mm/1.00"
2500E  2.70m106.3"  0.5 to 4.88 m/19.7-192.1"  30mm/1.00"

Mounting Height: 

In general, the aerosol generators should 

be mounted at or near ceiling height and angled toward the 

floor at an angle to ensure three-dimensional distribution of 

aerosol and an unobstructed discharge path. (15° - 30° for 

sidewall mounting). To ensure maximum distribution of aerosol 

throughout the hazard area, the maximum height of generator 

placement from the floor must be limited as indicated above. 

Underfloor applications should be mounted horizontally.

Flow:

 Placement of the aerosol generators to ensure proper 

aerosol flow and distribution is extremely important as each 

generator functions as a flow nozzle. 

Aerosol generators 

must never be positioned to discharge directly at each 

other! 

This will cause agglomeration of the aerosol particulate, 

reducing the aerosol’s extinguishing effectiveness. 

For the 

same reason, aerosol generators must be positioned to 

ensure that the aerosol stream does not impinge directly 

on walls or the sides of equipment being protected.

Typical Placement

Aerosol Generators

 

Equipment

C Zone

S

*

Equipmen

t

Equipmen

t

*Spacing “S” should be even unless prevented by obstruction.

Отзывы: