Stat-X 30E Скачать руководство пользователя страница 4

Owner’s Manual

6

7

4.  Securely attach generators to the mounting brackets with 

generator clamps taking care to ensure the clamps are free 

of the initiator mechanism and that all bolts are securely 

tightened. 

Aerosol gases discharged from the generator 

will add thrust loading on the clamps. It is essential that 

the fasteners are secure.

5.  Position generators, via the bracket-mounting swivel, to allow 

for unimpeded discharge upon activation. Care must be taken 

so that the generator does not directly discharge at close range 

on the wall, ceiling, or vertical surfaces of equipment within the 

hazard area. Generators must be positioned to promote circular 

flow and mixing of aerosol from multiple generators. Aerosol 

generators must never be positioned to discharge directly 

at each other! This will cause agglomeration of the aerosol 

particulate, reducing the aerosol’s extinguishing effectiveness. 

The aerosol system is designed to flood the protected space 

when the generators are positioned in a balanced arrangement. 

It is not required for the generators to be aimed at specific 

hazards as local application streaming devices.
6.  Generators can be wired in series or parallel to a releasing 

control panel. Activation current must be supplied to each 

generator as follows:
Activation parameters of the initiator are:

•  Resistance: 1.4 – 2.0 Ohms 

•  Minimum parallel circuit firing current: 0.5A for 0.050 

seconds.

•  Minimum series circuit firing current: 1.0A for 0.050 

seconds.

•  Specified maximum test current: 

0.025A.

•  Specified maximum supervisory current: 

≤.

005A.

7.  Install releasing control panel, detection, and ancillary 

devices per the directions contained in the manual supplied. 

Wiring is to be installed to local code requirements.
8.  Once the electrical components of the system have been 

installed and tested, ensure power is off and then connect 

electrical lines to the initiator fitting at the top of the generator. 

Post Installation Checkout: 

After the Stat-X generators have 

been installed and connected to the appropriate detection and/

or control system perform the following inspection and tests. 
1.  Verify generators of the correct size are installed per the 

installation drawings.
2.  Verify generator mounting brackets and clamps are properly 

installed and that all fittings and fasteners are tight.
3.  Verify electrical connections have been made and test for 

electrical continuity using an ohmmeter.
4.  Verify generators are positioned properly. Check for 

obstructions in the path of the aerosol discharge stream. 

Generators must be installed such that they cannot cause 

personnel injury upon activation. The aerosol discharge stream 

must not impinge at close range on walls, ceiling, or equipment. 
5.  Manual/electrical release stations must be properly 

installed, readily accessible, and clearly identified.
6.  Verify time delay functionality and integrity.
7.  All acceptance testing shall be in accordance with this 

manual, any applicable standards, and the authority having 

jurisdiction. 

OPERATION

General.

 A solid charge of the aerosol composition is 

contained within the sealed generator. Upon activation of the 

initiator, the charge begins a controlled burn producing an 

ultra-fine aerosol. The aerosol passes through an oxidation 

filter, where CO is converted to minor amounts of CO

2

, and 

then through a cooling bed where the temperature of the 

aerosol is rapidly reduced before it escapes through the 

discharge ports of the generator at low pressure. Generator 

placement within the hazard area provides proper flow and 

distribution of the aerosol within the protected area. 

Operating Procedures

Electrical Automatic Operation: 

Electrical automatic 

operation occurs upon activation of the detection circuit, 

initiating a voltage source from the fire alarm control panel to 

the generators. 
In areas where personnel may be present, a 30 second 

time delay is required to ensure egress time prior to system 

discharge. In normally occupied areas, a system maintenance 

isolate switch shall be installed outside the hazard area to 

ensure that activation of the system is “manual only” during 

maintenance of the system. 

Personnel must evacuate the hazard area promptly upon 

hearing the pre-discharge alarm. Ensure no one enters  

the hazard area after discharge and call the fire 

department promptly. 

NOTE

THE ABOVE INSTRUCTIONS MUST BE POSTED ON DISPLAY 

IN THE PROTECTED AREA. 
Remote Electrical Manual Operation:

 Manual electrical 

operation is performed by manual release from a releasing device 

located outside the protected enclosure. Operate as follows: 
1.  Upon fire notification, leave the hazard area quickly
2.  Proceed to the appropriate remote manual/electrical release 

station for the hazard. 
3.  Ensure all personnel have left the protected enclosure.
4.  Operate manual pull station.
5.  Allow no one to enter the hazard area. Call the fire 

department promptly.

Maintenance System Isolate Switch:

 Unless prohibited by 

the local authority having jurisdiction, the automatic operation 

of the system shall be prevented by means of a system isolate 

switch (lockout located outside the protected area) during 

maintenance when personnel are present. The operation of the 

system shall be manual only during maintenance operations 

on the fire detection system or on the generators. While the 

system isolate switch is active the automatic activation of the 

system is inhibited but the fire detection and alarm system 

shall continue to function. The system shall return to full auto-

matic control when the switch is reactivated. An abort switch 

may be installed to allow personnel to delay the automatic 

operation of the system.

Post Discharge Operation: 

After discharge of a Stat-X 

fire suppression system, qualified fire suppression system 

maintenance personnel must perform post discharge 

maintenance and system installation procedures outlined in 

this manual. Observe all warnings, especially those pertaining 

to the length of elapsed time before entering the hazard area. 

WARNING

DO NOT ENTER A HAZARD AREA WITH AN OPEN FLAME OR 

LIGHTED CIGARETTE. THE POSSIBLE PRESENCE OF FLAM-

MABLE VAPORS MAY CAUSE RE-IGNITION OR EXPLOSION. 

WARNING

WHILE MAINTAINING ENCLOSURE INTEGRITY, ENSURE 

FIRE IS COMPLETELY EXTINGUISHED PRIOR TO VENTILAT-

ING AREA. BEFORE PERMITTING ANYONE TO ENTER THE 

HAZARD AREA, VENTILATE AREA THOROUGHLY OR USE 

SELF-CONTAINED BREATHING APPARATUS.
Post Fire Operation:

 The following procedures must be 

followed in the exact sequence to maintain and re-commission 

Stat-X generators as part of a suppression system: 
1.  After discharge, allow a minimum holding time of ten (10) 

minutes 
2.  Always be sure to have backup portable extinguishers at 

hand for use in the event of re-ignition.
3.  Vent area thoroughly by operating the ventilation system, 

by fan extraction, or by opening doors and windows. Avoid 

opening doors leading to other occupied rooms. To avoid 

unwanted inhalation of fire by-products and aerosol, a 

protective breathing apparatus or mask should be worn if it  

is necessary to enter prior to complete ventilation of the 

hazard volume.
4.  Inspect the area to ensure the fire is completely 

extinguished and that there are no localized hot spots or other 

sources of re-ignition present.
5.  Clean residue which have not been removed during 

ventilation, by thoroughly vacuuming, blowing, brushing, or 

washing away (with a water and 3.5% vinegar or similar acetic 

acid solution) as appropriate. Check to make sure that there 

is no agglomeration due to discharge too close to equipment, 

walls etc. If any agglomeration exists it must be wiped or 

Отзывы: