Maglink 16T rev.08 2015-07 - ENG
36
When an alarm occurs a discontinuous beep is alerted and the event is stored into the SD card. Alarms need to be acknowledged,
pressing ESC key. This action will store the ACK event
into the SD card and the sound will be cleared.
If the alarm is restored by itself the beep will finish and the event will be stored into the SD card.
Lines can be of 3 different colors:
RED: alarm occurs NEW
YELLOW: alarm acknowledge ACK
GREEN: alarm cleared CLEAR
With UP and DOWN keys the alarm list is scrolled showing the last 150 stored alarms.
But there is no limit to the alarm stored into the SD card.
Date, time, tank number, alarm code and status are stored into the SD card.
Alarm codes listed as follow:
01
No Probe Link
Probe not answering, check address or cabling
02
High
Product level is over value H but under value HH if different from 0
03
Low
Product level is under value L but over value LL if different from 0
04
Out of Range
Product level is over the last value of the strapping table. It is not possible to calculate the
volume because data are missing
05
Probe
Probe is answering without valid measure. Check floats, bendings
06
High High
Product level is over HH value
07
Low Low
Product level is under LL value
10
Water
Water level is above the set value
00
No alarm
No alarm
12
Water + High
Water alarm + High product alarm combination
13
Water + Low
Water alarm + Low product alarm combination
16
Water + High High
Water alarm + High High product alarm combination
17
Water + Low Low
Water alarm + Low Low product alarm combination
Содержание MAGLINK 16T
Страница 1: ...INSTALLATION MANUAL CONSOLE MAGLINK 16T...
Страница 3: ...Maglink 16T rev 08 2015 07 ENG 3 30 07 15 8 GENERAL REVISION 11 X X...
Страница 29: ...Maglink 16T rev 08 2015 07 ENG 29...
Страница 43: ...Maglink 16T rev 08 2015 07 ENG 43 CERTIFICATION...
Страница 44: ...Maglink 16T rev 08 2015 07 ENG 44...
Страница 45: ...Maglink 16T rev 08 2015 07 ENG 45...
Страница 46: ...Maglink 16T rev 08 2015 07 ENG 46...
Страница 47: ...Maglink 16T rev 08 2015 07 ENG 47 NOTIFICATION...