SolConeX extra-low voltage wall-mounting socket
Series 8573/13
8
Commissioning
Before commissioning, ensure the following:
• Check the mounting and installation.
• Enclosure must not be damaged.
• If necessary, remove foreign bodies.
• If necessary, clean the connection chamber.
• Check if the conductors have been inserted correctly.
• Check if all screws and nuts have been tightened firmly.
• Check whether all the cable entries and stopping plugs have been tightened firmly.
• Check if all conductors have been clamped firmly.
• Observe the line voltage.
• Seal the unused cable entries with plugs certified according to Directive 2014/34/EU
or IEC and unused drilled holes with stopping plugs certified according to Directive
2014/34/EU or IEC.
9
Operation
Only type 8570/12 and 8575/12 plugs from R. STAHL may be used.
DANGER
Explosion hazard due to incorrect installation!
Non-compliance results in severe or fatal injuries.
• Check the device for proper installation before commissioning.
• Comply with national regulations.
WARNING
Damage or destruction of the device by arc and high pressure is possible
if improper switching operations are used!
Non-compliance can result in severe or fatal injuries.
• Quickly switch the device on and off completely.
• Avoid switching positions between 0 and I (ON and OFF).
The wall-mounting socket may only be operated when fully mounted.
The wall-mounting socket can be switched only with the plug inserted.
If the plug has been disconnected, close the hinged cover with the bayonet
ring.