Maintenance and Repair
14
150942 / 8571601300
2014-01-21·BA00·III·en·08
SolConeX Wall-Mounted Socket, 32 A
Series 8571/11
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
10
Maintenance and Repair
10.1 Maintenance
• Consult the relevant national regulations to determine the type and extent of
inspections.
• Adapt inspection intervals to the operating conditions.
During maintenance of the device, check at least:
• if the cables are clamped properly;
• the enclosure, seals and surface of the plug pins for damage;
• sleeves for pollution;
• compliance with the permitted temperatures in accordance with IEC/EN 60079-0;
• whether the device is used according to its designated use.
10.2 Maintenance
WARNING
Unauthorized work being performed on the device!
Risk of injuries and material damage!
• Work performed on the device must only be carried out by
appropriately authorized and trained personnel.
WARNING
Danger due to live components!
Risk of severe injuries!
• All connections and wiring must be disconnected from the power
supply.
• Secure the connections against unauthorized switching.
DANGER
Danger due to defective switching contacts!
Risk of injuries and material damage!
• Replace the entire socket flange after each short circuit in the main
circuit of the switch because the state of the switching contacts
cannot be checked in hermetically sealed equipment.
Observe the relevant national regulations in the country of use.