Safety switch / load disconnect switch
Series 8146/5-V37, Series 8150/5-V37,
Series 8146/5-V11
Mounting and dismounting protection against accidental contact
WARNING
Risk of electric shock due to twisted cable lug connection!
Non-compliance can result in severe or fatal injuries.
• To avoid mechanical load and twisted cables intall the protection
against accidental contact.
• Only operate the switch with installed protection against accidental
contact or with a separate anti-twist protection!
12441E00
• Remove the protective foil from the
insertion prism (6) and glue the insertion
prism in the main terminal (7).
• Insert the clamping plate (5) into the main
terminal (7) and tighten the mounting screw
of the main terminal (1) with 5 Nm (for 8544)
and 20 to 25 Nm (for 8549).
• Insert the conductor with ring cable lug (4)
and split washer (3) into the screw (M12) of
the clamping plate and tighten it by means
of the nut (2) 5 Nm (for 8544) and 50 Nm
(for 8549).
12442E00
• Attach the protection against accidental
contact (8) on the main terminal,
the clamping plate and the conductor.
• Dismounting is carried out in reverse order.
1
2
3
4
6
5
7
8