Mounting cover for Ex i auxiliary contact
7.2.2 Mounting Earthing Assemblies
Assembly 8195
Assembly 85
12436E00
• Attach the cover (4) from the top
to the auxiliary contact until it
engages into the lug.
03680E00
• Connection cross-section:
1.5 to 4 mm
2
• Tightening torque clamping unit:
2 Nm
07871E00
Protective conductor for cable
cross-section up to 10 mm
2
Outside:
• Loosen the screw (3).
• Insert the core under the
clamping bracket (4).
• Tighten (4.5 Nm) the screws (3).
Inside:
• Unscrew the screw (1).
• Insert the cable lug onto the
screw.
• Tighten the screw (1) together
with the cable lug (1.4 Nm).
4
1
2
4
3