The following applies to all terminals:
0.2 - 2.5 mm² / AWG24 - AWG14 for flexible cable
0.2 - 4 mm² / AWG24 - AWG12 for rigid cable
Strip cable of 7 mm (0.28 in) insulation
max. one cable per terminal
Recommended cable length for terminals X11, X12, X13, X14,
X24, X25:
max. 3 m (10 ft)
*
Please note that the Ethernet connection is
either
for an optical
fibre connection (X18)
or
for a copper connection (X16),
depending on the version ordered !
Up from HW-Rev. 01.01.02, all MT-4x7 and MT-5x7 devices with
SX Ethernet interface are fitted additional with an Ethernet TX
interface !
The option 2TX is only possible at devices with Bay Trail (BT)
processor and
NOT
at 600 SERIES !
The device MT-577-*-P2 has a second Ethernet TX (copper)
interface in the TX version (1TX not available).
If display types MT-xx7-DVI1-MM or MT-xx7-DVI1-SM (optical
fibre versions) are used, terminal X16 remains unused.
In the case of an optical fibre connection the following cable is
recommended:
Multi-mode optical fibre cable:
50 µm core cross section and 125 µm external cross section
Single mode optical fibre cable:
9 µm core cross section and 125 µm external cross section
**
The USBi2 connection (X25) is
NOT
available for devices with
touch screen and may
NOT
be connected.
The unused wires of X16 at version 2TX must be isolated
according to applicable regulations. This may be by means of
double isolation and mechanical fixing by shrink sleeving or
vulcanisation. The shrink sleeving or the vulcanisation must be
suitable for at least 500 V and be within the temperature
parameters of the device. The shrink sleeving / vulcanisation
must
NOT
be light blue. When the data cables are shortened, this
must also be kept in mind.