Maintenance and repair
18
250306 / MCP60300050
2015-10-23·BA00·III·en·00
Flameproof Manual Call Points
Series MCP/PB
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
9.1
Troubleshooting
If the error cannot be eliminated using the mentioned procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For fast processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended use (in particular input / output wiring)
10
Maintenance and repair
10.1 Maintenance
• Determine the type and extent of inspections in compliance with the relevant national
regulations.
• Adapt inspection intervals to the operating conditions.
The following tests and measures must be carried out during regular maintenance.
CAUTION
Risk of electric shock or malfunction of the device due to unauthorized work!
Non-compliance can result in light injuries!
• Before carrying out work on the device, switch off voltage supply.
• Work performed on the device must only be carried out by authorized
and appropriately trained qualified electricians.
Observe the relevant national regulations in the country of use.
Check
Measures
the permissible ambient temperature
If exceeding the permissible ambient
temperature or falling below the device
must be taken out of operation.
the enclosure components for formation
of cracks and damage.
Replace the exchangeable enclosure
components. If the enclosure components
are non-exchangeable, the device must be
taken out of operation.
its intended use
If the device is not used according to its
intended use, it must be taken out of
operation.
if the conductors are clamped properly
clamp loose conductors tightly.
the cables for ageing and damage
replace damaged or aged cables.
the seals for ageing and damage
replace damaged, aged and porous seals
and completely change enclosure
components with foamed seal.
Содержание MCP/PB