Supply Module
Type 9193/21-11-11
If the error cannot be eliminated using the specified procedures:
Contact R. STAHL Schaltgeräte GmbH.
For rapid processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended use (in particular, input and output wiring)
Error
Cause of error
Troubleshooting
Error message
from ISpac device,
no collective error
message from
9193/21-11-11
• One jumper on the
pac-Bus 9194/50-01
connection terminal
not removed
(Note:
The connection terminal
9194/50-01 comes with
two jumpers!)
• Error message deactivated
by DIP switch
• Remove the jumper on the
terminal that is adjacent to
the supply module 9193.
• Set DIP switch 2 or 3 to
position I.
"ERR" LED flashing,
ISpac devices are
not in operation
• Interchangeable fuse
defective or not installed
• Replace interchangeable
fuse, see Chapter 9.2.1,
or install and check whether
the pac-Bus segment has
been set up correctly and the
auxiliary power supply has
the correct voltage
"ERR" LED flashing,
no PWR error,
ISpac devices
are operational
• Error in one or more
ISpac devices on the
segment
• Connection terminal with
jumper not installed correctly
• Eliminate error in the
ISpac devices,
see operation instructions
of the respective device
• Correct mounting of the
connection terminal with the
jumper