Supply Module
Type 9193/21-11-11
Improper mounting, installation, commissioning, maintenance or cleaning
Basic work such as installation, commissioning, maintenance or cleaning of the device must
be performed only in accordance with the valid national regulations of the country of use and
only by qualified persons. Otherwise the explosion protection can be rendered ineffective.
This may result in explosions causing serious or even fatal injury to persons in the vicinity.
Have mounting, installation, commissioning and maintenance work performed only by
qualified and authorised persons (see Chapter 3.2).
Prior to commissioning, check the mounting for correctness (see Chapter 7).
Only mount the device on the NS 35/15 or NS 35/7.5 DIN rail in accordance with
IEC/EN 60715.
When used in Zone 22, the device is to be installed in a protective enclosure or in a cabinet
according to IEC/EN 60079-31. This enclosure (or cabinet) has a suitable degree of
protection (at least IP64).
When used in Zone 2, the device is to be installed in a protective enclosure or in a cabinet
according to IEC/EN 60079-0. This enclosure (or cabinet) has a suitable degree of
protection (at least IP54).
The device may only be operated in environments not exceeding degree of pollution 2.
When operated together with Ex i electrical circuits in Zone 2, protect the non-intrinsically
safe terminals with a covering that fulfils the the IP30 degree of protection. If the covering
is missing: Open the enclosure only in a de-energised state.
In hazardous areas, operate the DIP switch of the device only in a de-energised state.
In hazardous areas, always switch the electrical circuits to a de-energised state before
disconnecting or connecting and when mounting/dismounting devices on the pac-Bus.
Use only one 9193 device per pac-Bus segment.
Do not change or retrofit the device.
Gently clean the device only with a damp cloth and without scratching, abrasive or
aggressive cleaning agents or solutions.
4
Transport and Storage
Transport and store the device carefully and in accordance with the safety notes
(see Chapter "Safety").