Parameterization and Commissioning
22
169128 / 944160310050
2020-08-25·BA00·III·en·08
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Ethernet CPU module and
power module for Zone 1/Class I, Div.1
Series 9441, Series 9444, Series 9492
Changing the Subnet mask
LCD display
Settings
Press the [Enter] key twice to switch from the system level to the
information/service level.
12309E00
Press the [Enter] key once if the display shows
"CPU 0-0: primary; 9441/12-00-00" in order to switch from the
system level to the information/service level.
The following display appears (shown on the left).
12310E00
Press the ◄ or ► key until the following display appears
(shown on the left).
12311E00
Press the [Enter] key.
The following display appears (shown on the left).
12314E00
Press the ◄ or ► key until the following display appears
(shown on the left).
Press the [Enter] key.
The first address block is marked.
Press the ◄ or ► key until the required value is displayed.
12315E00
Press the [Enter] key.
The change to the first address block is applied.
The second address block is marked.
Change the second to fourth address blocks in the same way as the
first address block.
12313E00
Press the [Enter] key.
The following display appears (shown on the left).
Press the [Enter] key to confirm the change to the address.
The display switches back to the main menu in the information/
service level.
CPU 0-0: Status
NoDataExch
CPU 0-0:Address
<
>
IpAdr
192. 23.121.7
<
>
SubNet
<
>
255.255.255.0
255
254
252
248
240
224
192
128
0
◄:
►:
accept changes ?
< >
no
yes