Ethernet CPU module and
power module for Zone 1/Class I, Div.1
Series 9441, Series 9444, Series 9492
12336E00
Plug the DIN rail (17) into the terminal (X5 or X6) and screw it to the mounting plate
(tightening torque: 2.6 Nm).
Insert the BusRail section (18) into the DIN rail and carefully push it onto the terminal.
Clip the ground clamps (19) above the DIN rail.
Place the I/O module on the first slot in order to check the position of the BusRail in relation
to the socket. The BusRail has engaged correctly when the I/O module is positioned
directly on the socket.
Loosen the ground clamps (19), correct the position of the BusRail and clip the ground
clamps back above the DIN rail.
Tighten the clamping screw (15) on the terminal (X5 or X6) (tightening torque: 2 Nm).
Mount the BusRail end (20) at the end of the BusRail section.
Mounting the BusRail using a connecting cable (type 9494/L1-V)
12335E00
Loosen the clamping screw (15) on the terminal (X5 or X6) and remove the
terminal cover (16).
(