260520 / 640960300090
2018-11-08·BA00·III·en·02
Operation
27
Emergency Luminaire with LED
Series EXLUX 6409/1
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
• takes 1 minute.
• checks the function of the LEDs and the battery.
Rated operating time test
• starts within 44 days after commissioning.
• is carried out once a year.
• checks the function and the operating time of the luminaire during emergency light
mode.
• is repeated after 14 days if rated operating time test is faulty.
10.3 Indications
When connecting to the power supply
Initialisation within 10 seconds
After that, the LED indicator switches to the operating mode.
During power supply operation
Blinking: 1 second on, 1 second off
Flashing: 0.25 seconds on, 0.75 seconds off
Second
Description
0 - 2
Function test LED
indicator "green"
2 - 4
Function test LED
indicator "red"
4 - 10
Status rated operating
time test
LED indicator flashes green - rated operating
time test active
LED indicator off - rated operating time test
deactivated