![Stahl 9182 Series Скачать руководство пользователя страница 34](http://html1.mh-extra.com/html/stahl/9182-series/9182-series_operating-instructions-manual_1357858034.webp)
Operation
16
167450 / 9182603310
2021-12-07·BA00·III·en·06
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Temperature transmitter
non-Ex i field circuit
Series 9182
10.2 Displays
The corresponding LEDs on the device indicate the operating state of the device
(see also chapter "Function and device design").
*) Activation of line fault detection using the DIP switch "LF1"
10.3 Troubleshooting
For troubleshooting, refer to the following troubleshooting guide:
If the error cannot be eliminated using the specified procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For rapid processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended purpose (especially input/output circuit)
LED
Colour "ON" LED
"OFF" LED
"PWR" LED
green Device is supplied with auxiliary power Device is not in operation,
power supply not available
"LF1" LED *)
red
Line fault in signal of channel 1
No line fault in signal of channel 1
flashing Outside measuring range
"A" LED
yellow Limit contact A active
Limit contact A not active
"B" LED
yellow Limit contact B active
Limit contact B not active
Error
Cause of error
Troubleshooting
"PWR" LED is off
• Auxiliary power failure
• Polarity reversal of the
auxiliary power supply
• Defective miniature fuse
• Monitor the polarity of the auxiliary
power supply.
• Monitor the wiring of the auxiliary
power supply.
• If the fuse is defective, have the device
repaired.
"PWR" LED flashes
permanently
Defective device
Send the device in for repair.
Defective output signals
• Incorrect connection of the
sensor
• Incorrect setting of the DIP
switch
• The device is programmed
via PC, but the DIP
switches are not in the
"OFF" position
• Check the connections.
• Adjust the DIP switch correctly.
• Set the DIP switch "S2...1" to the
"OFF" position.
Line compensation is
not functioning
• Compensation disabled
• Line resistance is too high
• Set the DIP switch "S2" to the "OFF"
position.
• Perform compensation.
• Bridge the sensor.
"LF1" LED lights up
Line fault at the input
Check the connections.
"LF1" LED is flashing
Outside measuring range
Configure the measuring range accordingly.
Содержание 9182 Series
Страница 37: ......