Mounting and Installation
12
167450 / 9182603310
2021-12-07·BA00·III·en·06
DE
EN
FR
IT
ES
RU
NL
DK
SE
FI
PT
GR
PL
CZ
SK
HU
SL
RO
BG
LV
LT
EE
CH
KR
CN
Temperature transmitter
non-Ex i field circuit
Series 9182
Dismounting
8.2.3 Mounting/Dismounting on pac-Carrier
See operating instructions for pac-Carrier type 9195.
8.2.4 Mounting/Dismounting pluggable Terminals
All devices are equipped with pluggable terminals.
Mounting
• Insert the terminal into the device until the terminal engages.
Dismounting
8.3
Installation
8.3.1 Electrical Connections
06881E00
• Pull out the base bolt slightly using a screwdriver.
• Swivel out the device.
10859E00
• Position the screwdriver behind the terminal.
• Push out the terminal.
Operation under difficult conditions, e.g. on ships in particular,
requires additional measures to be taken for correct installation,
depending on the operating location. Further information and instructions
on this can be obtained on request from your designated sales contact.
NOTICE
Malfunction or device damage caused by non-shielded field cables.
Non-compliance may lead to material damage!
• If the system has strong electromagnetic sources of interference or the
electrical lines are longer than 30 m, shielded field cables must be used.
• The shield must be connected to the equipotential bonding and placed on
the shield buses in the enclosure as close to the entry point as possible.
• The shield buses must also be connected to the mounting plate close to the
entry point of the field wiring using the shortest possible route.