english
Operating Instructions
Switching Repeater Type 9170/*2
9
7.3
Settings
Line fault detection (LF)
Line of action inverted (INV)
deactivated *)
activated
OFF *)
ON
Channel 1
Channel 2
*) Default factory setting
8
Operation and operational states
Output state
for “line of action inverted” (see 7.3)
Input
Input current
OFF
ON
Line fault detection LF = deactivated
Proximity switch high
impedance / Contact:
open / open circuit
I
E
≤
1.2 mA
Relay not energized /
Electronic output
deactivated
Relay energized /
Electronic output activated
Proximity switch low
impedance / Contact:
closed / short circuit
I
E
≥
2.1 mA
Relay energized /
Electronic output activated
Relay not energized /
Electronic output
deactivated
Line fault detection LF = activated
Open circuit
I
E
≤
0.05...0.35mA
Relay not energized /
Electronic output
deactivated
Relay not energized /
Electronic output
deactivated
Proximity switch high
impedance / Contact:
open
I
E
= 0.35…1.2 mA
Relay not energized /
Electronic output
deactivated
Relay energized /
Electronic output activated
Proximity switch low
impedance / Contact:
closed
I
E
= 2.1…5 mA
Relay energized /
Electronic output activated
Relay not energized /
Electronic output
deactivated
Short circuit
R
E
≥
100..360
Ω
Relay not energized /
Electronic output
deactivated
Relay not energized /
Electronic output
deactivated
LF1
LF2
INV1
INV2
ON
OFF
1
2
LF1
LF2
INV1
INV2
ON
OFF
1
2
LF1
LF2
INV1
INV2
ON
OFF
1
2
LF1
LF2
INV1
INV2
ON
OFF
1