Страница 1: ...Type 9170 Switching Repeater 1 1 1 Operating Instructions Type 9170 2 Switching Repeater...

Страница 2: ...Engineering of the power dissipation in cabinets 6 6 Arrangement and fitting 7 6 1 Dimensions 7 6 2 Installation 7 6 3 Mounting and dismounting 7 7 Commissioning 8 7 1 Connections 8 7 2 Engineering 8...

Страница 3: ...lly recognised technical regulations Safety guidelines in these operating instructions Any damage can compromise and even neutralise the explosion protection The following requirements apply if used i...

Страница 4: ...ternal capacitance Ci Internal inductance Li Max connectable capacitance Co IIC IIB I Max connectable inductance Lo IIC IIB I Insulation voltage Um 9 6 V 9 6 V 10 mA 20 mA 24 mW 48 mW 2 42 nF 4 84 nF...

Страница 5: ...F 149 F 9170 22 12 23 131 F 149 F Ventilation With ventilation Installation Single unit DIN rail Orientation any vertical horizontal Channels Type 1 9170 12 12 13 158 F 158 F 158 F 9170 12 12 23 158...

Страница 6: ...e lower and upper ends of the cabinet the air flow path must be kept free from obstacles Result Depending on the engineering the improvement can reach a two times higher power dissipation as with a c...

Страница 7: ...napping onto the pac Bus Note In order to prevent pole reversal during installation the pac Bus elements have been equipped with a keyed connection plug see photo The module is fitted with a matching...

Страница 8: ...t identification volt free contacts at the input Open circuit identification 22 k or 33 k in parallel Short circuit identification 2 7 k in series The loading has to carry out in direct proximity of t...

Страница 9: ...ized Electronic output activated Relay not energized Electronic output deactivated Line fault detection LF activated Open circuit IE 0 05 0 35mA Relay not energized Electronic output deactivated Relay...

Страница 10: ...neration of High Level is missing The High Level can be generated if an resistor is connected externally to the supply voltage e g 5V Self test In order to check basic functions of the device you may...