Transmitter Supply Unit with Limit Values
Series 9162
10
Operation
10.1 Indications
The corresponding LEDs on the device indicate the operating conditions of the device
and the line fault states (also refer to chapter "Function and Device Design").
10.2 Troubleshooting
Observe the following troubleshooting plan for troubleshooting:
If the error cannot be eliminated using the mentioned procedures:
• Contact R. STAHL Schaltgeräte GmbH.
For fast processing, have the following information ready:
• Type and serial number of the device
• Purchase information
• Error description
• Intended use (in particular input / output wiring)
Selection in ISpac
Wizard
Description of the function "anti-pumping device"
"Deactivated"
Default setting - function is off
"Activated"
Function as described above. When the event occurs,
the set operating mode ("OFF") does not change.
The anti-pumping device is reset by actuating the DIP switch
"RL" (OFF-ON-OFF or ON-OFF) or by switching the device
or the ISpac Wizard off and on briefly. If, at the same time,
an error occurs, the limit value relays switch to the ON position
(example: "OFF above limit value" -> in case of error: OFF).
LED
Col
-
our
LED "ON"
LED "OFF"
"PWR" LED green Device is supplied with
auxiliary power
Device is not in operation,
voltage supply not available
"LF" LED
red
Line fault in signal
No line fault in signal
"A" LED
yellow Limit contact A active
Limit contact A not active
"B" LED
yellow Limit contact B active
Limit contact B not active
Error
Cause of error
Troubleshooting
"PWR" LED is off
• Auxiliary power failure
• Defective device fuse
• Polarity reversal of the
auxiliary power supply
• Check the polarity of
the auxiliary power supply.
• Check the wiring of
the auxiliary power supply.
• If the fuse is defective,
have the device repaired.