Function/troubleshooting
14
167921 / 862460300010
S-BA-8624/1-01-en-30/07/2008
Control unit Ex p
8624/1
Fault during normal operation
Normal operation is automatically deactivated if:
X
Power supply fails for more than 2 seconds
X
The internal pressure of the enclosure falls below the set MIN value
(factory settings: 0.8 mbar)
X
The internal pressure of the enclosure exceeds the set MAX value
(factory settings: 15.0 mbar)
Fig. 8-4: Fault during normal operation
)
After having eliminated the fault, the control unit is activated automatically.
The control unit starts a new purging process if the pressure had fallen below
the MIN value.
T1:
Purging is finished.
The preset internal pressure of the enclosure is adjusted (2 bar).
The devices in the Ex p enclosure are connected.
T2:
Normal operation starts.
The internal pressure is adjusted to the nominal value (2 bar).
T3:
The internal pressure starts falling.
The devices in the enclosure are switched off when reaching the MIN value.
T4:
Repeated purging.
T5:
Normal operation starts.
T6:
The internal pressure starts increasing. The increased internal pressure cannot
escape via the mechanical valve of the control unit.
T7:
The devices in the enclosure are switched off when reaching the MAX value.
T8:
After pressure relief, normal operation starts again without repeated purging.
0,0
10,0
8,0
6,0
4,0
2,0
T1
T2
T3
12,0
20,0
18,0
16,0
14,0
T4
T5
T6
T8
T7
Содержание 8624-1
Страница 1: ...Betriebsanleitung Operating Instructions Steuereinheit Ex p Control unit Ex p 8624 1...
Страница 2: ......
Страница 3: ...Betriebsanleitung Steuereinheit Ex p 8624 1...
Страница 31: ...Operating Instructions Control unit Ex p 8624 1...
Страница 58: ......
Страница 59: ......
Страница 60: ...167921 862460300010 S BA 8624 1 01 de en 30 07 2008...