Control unit Ex p
8624/1
7.2 Setting of the leakage air volume at the air supply unit
06079E00
* pressure set on pressure controller
Fig. 7-2: Leakage air diagram
06080E00
Fig. 7-3: Setting the leakage air volume
X
Close the adjusting screw on the solenoid valve in clockwise direction as far as
possible.
X
Turn the adjusting screw in anti-clockwise direction until the desired leakage air
volume is reached (see leakage air diagram, Fig. 7-2)
)
The leakage nozzle is set at factory to an air volume of 15 l/min,
at a pressure of 2 bar.
The pressure controller is set at factory to a pressure of 2 bar.
0
10
20
30
40
50
60
70
80
90
100
0
0.5
1.5
2.5
3.5
4.5
1
2
3
4
5
[l/min]
2 bar*
2.5 bar*
3 bar*