Terminal Boxes
Series 8146/1, Series 8146/2
Fitting of additional terminals by the customer
Modify the device carefully and only in accordance with the safety notes
(see "Safety" section).
Ascertain additional terminal points, terminal type, quantity, cross-section and current
load.
Check whether type plate data is changed as a result of subsequently equipping
(cross-section, voltage, current, etc.).
Check whether enough space and fastening options are available for equipping.
5.4.3 Fuses
When fitting fuses, the ambient temperature values for the following temperature classes
apply:
When fitting fuses, the ambient temperature values for areas with dust explosion hazard for
the following max. permissible surface temperatures apply:
Subsequent equipping is not permitted if the installation conditions are not complied with!
Installing, modifying or retrofitting fuses is only permitted to be performed by R. STAHL!
Fuse current value
Temperature class
(
4 A
T6
> 4 A to
(
5 A
T5
> 5 A to
(
6.3 A
T4
Fuse current value
Ambient temperature
(Ta)
Max. permissible surface
temperature
(
4 A
(
40 °C
T80°C
(
4 A
(
56 °C
T95°C
(
5 A
(
46 °C
T95°C
(
6.3 A
(
70 °C
T130°C