INSTALLATION AND USER MANUAL
200TDHW
22
V0REV1EN0218
Setting
Values
Information
I1
1 or 2
1 = Indoor setting. Heat pump air source is from local room.
2 = outdoor setting. Heat Pump air source is from outdoor
I2
0
(Default)
or 1
1 = Off-peak installation. Water heater is installed in Off-peak
configuration. Off-peak wiring signal is connected and
operational
0 = Off-peak disable.
I3
Off
(default)
to 20
Off = PV function Off (Default)
Value from 1 to 20 = Minimum Sun exposure duration before
PV ON in Minute.
I4
0 or 1
1= Anti-legionella ON / 0 = Anti-legionella OFF
t’1
2 digits
NTC1 temperature value
t’2
2 digits
NTC2 temperature value
t’3
2 digits
NTC3 temperature value
t’4
2 digits
NTC4 temperature value
Setting
Values
Informations
T1
0 or 1
1= 30s of compressor test
T2
0 or 1
1 = 30s of Heating element test
T3
0 or 1
1 = 30s of fan speed 1 test
T4
0 or 1
1 = 30s of fan speed 2 test
T5
0 or 1
1 =30s of Electrovalve test
11.18.
DIAGNOSTIC
The controller gives an error code in case of abnormal operation.