20
Controllers
3. Function test
n
Disconnect sensors on terminals 3, 4, 5 and 6
n
Short terminals by leads. Short terminals 3 and 5 by one lead, and 4 and 6 by the second
one. After switching on, two control lights will turn on green (OK 3/5 and OK 4/6) and
output-relays will be activated.
n
In case of safety units with manual blocking, only one light will turn on. Press RESET in
order to reset the safety unit.
n
If terminals 3 and 4 or 5 and 6 are short, then both channels (K1 and K2 releases) will be
deactivated.
n
If we break connection on 3/5 terminals, K1 relay will be deactivated.
n
If we break connection on 4/6 terminals, K2 relay will be deactivated.