8. Modify the G file.
For details on the G file layout and how to configure the G file, refer
to section 7.1.
For this quick start, set the following words:
Word 1 - 8000h
Word 63 - 3543h (13635 decimal) (scanner module ID)
All other words can be set to 0000h.
Once you verify your system is operating correctly, you can
configure the rest of the network in the G file.
9. Use the provided serial cable to connect the scanner to your
configuration computer via the Config RS232 port.
10. Run your terminal emulation software. Set the baud rate to 38400
and the parameters to No parity, 8 data bits and one Stop bit. Press
the [*] key to get the scanner’s attention. Choose the network to
configure.
11. Hook up AS-i power and add an AS-i slave.
12. In your terminal software, perform a
List
command and verify the
slave appears on the network.
If the slave is listed at address 0, use the
Address
command to
change it to the desired address. Refer to section 6.5 for an example
of configuring a slave.
Continue adding slaves and setting their addresses.
13. Save the configuration and exit Config mode.
14. Put the SLC in run mode. This starts the scanner module scanning
I/O. Verify that you can read inputs and write outputs.
Содержание SST-ASI-SLC
Страница 6: ...SST ASI SLC User s Guide vi Conformance Statement 63 CE Notice 67 C D...
Страница 13: ...7 This chapter contains a system overview information on hardware features 2 Overview...
Страница 20: ...SST ASI SLC User s Guide 14...
Страница 30: ...SST ASI SLC User s Guide 24 IOM Ladder Logic Instruction...
Страница 44: ...SST ASI SLC User s Guide 38...
Страница 66: ...SST ASI SLC User s Guide 60...
Страница 68: ...SST ASI SLC User s Guide 62 AS i Power consumption 50 mA Phoenix connector part number MSTB 2 5 4 ST 5 08...
Страница 72: ...SST ASI SLC User s Guide 66...
Страница 74: ...SST ASI SLC User s Guide 68...