User Manual
Universal Serial/PROFIBUS DP Gateway
GT200-DP-RS
WWW.SSTCOMM.COM
57
Baud rate (bps):
Configure serial baud rate, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200bps
can be selected.
Data bits
,
Parity bit
,
Stop bits:
8 None 1, 8 Odd 1, 8 Even 1, 8 Mark 1, 8 Space 1, 8 None 2 Optional.
Protocol Type:
It depends on the device type (GSD file). For “GT200-DP-RS Serial V6.0” device, it acts as a
Serial device.
Receiving Frame Type:
“Time Interval Between Characters” (character timeout) and “Frame Length” (number of
characters) optional. Select the way to capture the data frames.
Time Interval Between Characters: Breaks the frames according to the time interval between characters.
Frame Length: Breaks the frames according to the data length (number of characters).
Interval Between Characters (ms):
The time interval between characters. When selecting “Time Interval
Between Characters” in Receiving Frame Type, if the interval time between characters exceeds the set time, the
data received before are regarded as a a frame.
Frame Length:
The number of characters in a frame. When selecting “Frame Length” in Receiving Frame Type,
every data of the set length are regarded as a frame.
Enable Auto Sending:
If enable, the output data will be sent automatically according to the Period of Auto
Sending. If disable, the output data is sent according to the working principle in
Period of Auto Sending (ms):
The period to send output data when enabling Auto Sending.
Enable CRC Check:
Enable and Disable optional. If enable, it adds the CRC check bytes for the output data.
When receiving data, it checks the CRC and filters the CRC bytes of correct frames.
Communication Interface:
RS485 and RS232 optional.
Input Data Effective Length:
The input data length. If enable, the received frame indicates the data length in
“Data length” (see
). If disable, the related value is fixed “11”.