User Manual
Universal Serial/PROFIBUS DP Gateway
GT200-DP-RS
WWW.SSTCOMM.COM
35
Enable Auto Sending is Enabled
Enable CRC Check
: Enable, Disable optional
Communication Interface:
RS-232, RS-485 optional. (Note: If using the RS-422, here select RS-485)
Time interval between Characters (Sending)
: The serial port of the GT200-DP-RS will send every byte
according to the time interval. The range of the value is 0 to 600, and the unit is 0.1ms. If the value is 100, then
the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of the
Modbus protocol)
Time interval between Characters (Receiving)
: The serial port of the GT200-DP-RS will use this time interval
as the judge receiving end basis. The range of the value is 0 to 600, and the unit is 0.1ms. If the value is 100, then
the time interval is 100* 0.1 ms =10ms. (Note: The time interval does not contain/cover the frame interval of the
Modbus protocol)
6.4.3 Interface of Node Configuration View
When the protocol type of the subnet is "Modbus Master", in the interface of device view, left click a node and
then the configuration interface will appear as shown as follow:
In this window, you can modify the Modbus slave node address in the configuration view interface.
6.4.4 Interface of Command Configuration View
In the interface of device view, left click a command and then the configuration interface window shown as
follow: