User manual - 1.2
English
39
7.4
Resetting the unit
1.
Press M
ENU
. Select
User menu
>
Manual
operation
using
S
and
T
. Press E
NTER
.
2.
Select
Manual operation reset
using
S
and
T
. Press E
NTER
.
Err 13 Refill freq. too high
Refilling takes place too frequently.
There is a leak in the installation.
Repair the leak.
Check the setting
Max. refill
freq.
Err 14 Refill time too high
Refilling takes too long.
There is a leak in the installation.
Repair the leak.
Check the setting
Alarm refill
after:
Err 15 Refill quantity
Too much is added.
There is a leak in the installation.
Repair the leak.
Check the setting
Alarm refill
.
1) The refill mode remains active, this applies to types S6A-R and S6A-R 2P.
Specific for types S6A-R and S6A-R 2P
Problem
Possible cause
Correction