INSTALLATION AND
COMMISSIONING
5.1
Installation conditions
•
Install the unit on a frost-free, well-ventilated place.
•
Electrically connect the unit to a 230 V / 50 -60 Hz
socket.
•
Make sure the expansion system has the proper
dimensions. The water displacement in the unit can
cause pressure variations in the installation.
•
There must be overpressure in the installation. This
prevents spontaneous aeration.
5.2
Unpack
The unit is delivered on a pallet.
1.
Remove the packaging.
2.
Loosen the 2 screws (A).
3.
Remove the cover (B) from the unit.
4.
Move the unit with two persons to the place of
installation. Lift the unit using the handles (C).
5.3
Installation and mounting
WARNING
Do not hoist the unit when unpacked. The use
of webbing slings, chains and hooks can
cause irreparable damage.
C
A
B
A
CAUTION
•
Install the unit in accordance with the
local guidelines and rules.
•
Install the unit as bypass on the main
transport line of the installation.
NOTE
•
Preferably install the unit at the point in
the installation with the lowest
temperature. Here the most dissolved
gases are found in the fluid.
•
Make sure when installing that the
operating panel is always easily
accessible.
•
Make sure you maintain a minimal
distance for service and repair as
indicated in the below.
•