Mounting
1.
Wall mounting
: Mount the unit on the wall using
the holes (A). Make sure that the mounting can
carry the filled unit (empty 10 kg).
2.
Floor mounting
: Place the unit on a flat surface.
Mount the unit on the floor using the holes (B).
5.3.2
Installation
Mechanical
1.
Make two branch lines ¾” (A) on the side of the
main transport line. The distance between them
should be at least 500 mm.
2.
Insert a valve (B) in each branch. With this the unit
can be depressurised.
3.
Connect the line (A) to the flexible outlet hose (D).
4.
Connect the line (B) to the flexible inlet hose (C).
With the types S6A-R and S6A-R 2P:
1.
Insert a valve (F) and a non-return protection (E) in
the refill fluid supply line.
2.
Connect the supply line to the refill connection (G)
of the unit.
CAUTION
Make sure that the valves are opened before
putting the unit into operation.
B
A Ø10
Ø10
A
500mm
A
B
B
>
NOTE
As seen from the direction of the volume flow,
the first branch is the inlet into the unit.
CAUTION
•
Use a locally approved non-return
protection. A non-return protection can
be optionally delivered.
•
Make sure that the pressure in the refill
line is below the system pressure. This
prevents undesired refilling in case of
failure of the refill line.
•
Make sure that the lines leave the unit at
the rear.
A
D
B
C
F
E
G