IM-P706-03
CTLS Issue 1
51
SP7-20 Smart Positioner
6.4 Message codes
Message codes
Message description
BREAK
Action stopped by operator.
CALC_ERR
Error during plausibility check.
COMPLETE
Action completed, acknowledgment required.
EEPR_ERR
Memory error, data could not be saved.
FAIL_POS
Safe position is active, action cannot be executed.
NO_F_POS
Safe position required, but not active.
NO_SCALE
Valve range limits have not yet been determined; therefore, partial
Auto Adjust cannot be run.
NV_SAVE
Data is saved in the non-volatile memory.
OUTOFRNG
Measuring range is exceeded, Auto Adjust was automatically
stopped.
LOAD
Data (factory settings) are being loaded.
RNG_ERR
Less than 10 % of the measuring range is used.
RUN
Action running.
SIMUL
Simulation has been started externally from a PC via HART
protocol; switch outputs, alarm output and analog position
feedback are no longer influenced by the process.
SPR_ERR
Actual spring action is different from the adjusted one.
TIMEOUT
Time-out; parameter could not be determined within two minutes;
Auto-adjust was automatically stopped.