IM-P706-03
CTLS Issue 1
46
SP7-20 Smart Positioner
5.3.2 SP7-21/22 Parameter overview
Parameter
Display
Function
Possible
parameter
setting
Unit
Factory
setting
P6.4
ADJ_MODE
Auto adjust
mode
Dead angle 0 %
FULL, STROKE,
CTRL_PAR,
ZERO_POS, LOCKED
---
FULL
P6.5
EXIT
Return
Return to
operating level
Function
---
NV_SAVE
P7._
CTRL_PAR
P7.0
KP UP
KP value, up
KP value (up)
0.1 to 120.0
---
1.0
P7.1
KP DN
KP value,
down
KP value (down)
0.1 to 120.0
---
1.0
P7.2
TV UP
TV value, up
TV value (up)
10 to 450
msec
100
P7.3
TV DN
TV value,
down
TV value (down)
10 to 450
msec
100
P7.4
GOPULSUP
Go pulse up
---
0 to 200
msec
0
P7.5
GOPULSDOWN
Go pulse,
down
0 to 200
msec
0
P7.6
Y-OFSUP
Y offset up
Y offset up
Y-Min to 100.0
%
40.0
P7.7
Y-OFSDN
Y offset down
Y offset down
Y-Min to 100.0
%
40.0
P7.8
---
---
P7.9
TOL_BAND
tolerance
band (zone)
Tolerance band
(zone)
0.3 to 10.0
%
0.8
P7.10
TEST
Test
Test
Function
---
INACTIVE
P7.11
EXIT
Return
Return to
operating level
Function
---
NV_SAVE
P8._, P9._,
P10._
P11._
FS/IP
P11.0
FAIL_POS
Safe postiton
Safe position
ACTIVE, INACTIVE
---
INACTIVE
P11.1
FACT_SET
Factory
setting
Factory setting
Function
---
---
P11.2
IP-TYP
I/P module
type
Type of I/P
module
NO_F_POS,F_
SAFE_1,F_SAFE_2,
F_FREEZE1, F_
FREEZE2
---
NO_F_POS
P11.3
EXIT
Return
Return to
operating level
Function
---
---
*Activation by Spirax Sarco Service only
Note:
For detailed information on the parameterization of the device, consult the associated configuration
and parameterization instructions.