IM-P706-03
CTLS Issue 1
15
SP7-20 Smart Positioner
2.
Using the arrow marks (4), check whether the lever moves within the operating range (between the
arrows).
3.
Hand-tighten the screw (7) on the lever.
4.
Hold the prepared positioner (with the mount bracket 1 still loose) on the actuator so that the follower
pin for the lever enters the follower guide to determine which tap holes on the positioner must be used
for the mount bracket. Refer to mounting table fig (tbc)
5.
Secure the mount bracket 1 with screws 2 and washers 3 using the relevant tap holes on the
positioner housing. Refer to mounting table fig (tbc)
Tighten the screws as evenly as possible to ensure subsequent linearity. Align the mount bracket in the
oblong hole to ensure that the operating range is symmetrical Set the valve mid stroke and align the lever
horizontal (item 4 Fig. 7) then tighten mounting bolt (item 4 Fig. 10) (lever moves between the arrow marks
Item 4 Fig. 9).
3.1.5 Mounting on a cast iron yoke
Fig. 7
1.
Attach the mount bracket (2) with screw (4) and washer (3) to the cast iron yoke (1)
Содержание SP7-20
Страница 9: ...IM P706 03 CTLS Issue 1 9 SP7 20 Smart Positioner...
Страница 39: ...IM P706 03 CTLS Issue 1 39 SP7 20 Smart Positioner Fig 21 5 2 SP7 20 HART Parameter Overview...
Страница 55: ...IM P706 03 CTLS Issue 1 55 SP7 20 Smart Positioner...
Страница 56: ...IM P706 03 CTLS Issue 1 56 SP7 20 Smart Positioner...